E5CK-T
E5CK-T
170
J
OPTIONAL OUTPUT BOARDS
Description
Specifications
Compatible controller
Max. quantity
Part number
Relay/Relay
SPST/SPST, 5 A, 250 VAC
E5CK-T
1
E53-R4R4
Relay/Pulse
SPST, 5 A/NPN, 24 VDC
E5CK
1
E53-Q4R4
SPST, 5 A/PNP, 24 VDC
E5CK
1
E53-Q4HR4
Relay/Linear current
SPST, 5 A/4–20 mA
E5CK
1
E53-C4R4
SPST, 5 A/0-20 mA
E5CK
1
E53-C4DR4
Relay/Linear voltage
SPST, 5 A/0-10 VDC
E5CK
1
E53-V44R4
Pulse/Pulse
NPN/NPN, 24 VDC
E5CK
1
E53-Q4Q4
PNP/PNP, 24 VDC
E5CK
1
E53-Q4HQ4H
Computer communications
RS-232C
E5CK
1
E53-CK01
RS-485
E5CK
1
E53-CK03
Event input
For remote set point
E5CK
1
E53-CKB
Transfer output
4 to 20 mA
E5CK
1
E53-CKF
Note: If the control period is less than 5 seconds, use an SSR (solid state relay) or pulse voltage output.
J
ACCESSORIES (ORDER SEPARATELY)
Description
Specifications
Compatible controller
Max. quantity
Part number
Current transformer; order
50 A load, 5.8 mm hole dia.
E5CK-T
1
E54-CT1
only if using heater
burnout alarm function
120 A load, 12 mm hole dia.
E5CK-T
1
E54-CT3
Terminal cover (supplied
with Standard models)
Provides finger protection from
terminals (VDE0106 part 100)
E5CK-T
1
E53-COV07
Software
For setup and monitoring;
requires optional computer
communications board
All
1
SYS-CONFIG V2.0
Temperature Ranges
Platinum Resistance Thermometer
Input
(switch selectable)
JPt100
Pt100
Range
°
C
–199.9
°
to 650.0
°
–199.9
°
to 650.0
°
°
F
–199.9
°
to 999.9
°
–199.9
°
to 999.9
°
Resolution
°
C/
°
F (main setting and alarm)
0.1
0.1
Thermocouple
Input (switch
selectable)
K1
K2
J1
J2
T
E
L1
L2
U
N
R
S
B
W
PLII
Range
°
C
–200
to
1,300
0.0 to
500.0
–100
to 850
0.0 to
400.0
–199.9
to
400.0
0 to
600
–100
to 850
0.0 to
400.0
–199.9
to
400.0
–200
to
1,300
0 to
1,700
0 to
1,700
100 to
1,800
0 to
2,300
0 to
1,300
°
F
–300
to
2,300
0.0 to
900.0
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
0 to
1,100
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
–300
to
2,300
0 to
3,000
0 to
3,000
300 to
3,200
0 to
4,100
0 to
2,300
Resolution
°
C/
°
F (main
setting, alarm)
1
0.1
1
0.1
0.1
1
1
0.1
0.1
1
1
1
1
1
1
Note: 1. Setting number is factory-set to 2 (K1).
2. Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Input (switch selectable)
Current input
Voltage input
4 to 20 mA
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
Range
One of following ranges depending on results of scaling
–1999 to 9999
–199.9 to 999.9
–19.99 to 99.99
–1.999 to 9.999
Resolution (main setting and alarm)
Depends on range selected