E5CK-T

  E5CK-T

186

J

PARAMETER OPERATION

Refer to “Settings” in the Operation Section.

Level 0 Mode

Process Value
Set Point

Pattern Number
(With E5CK–T, this display appears when more
than two patterns are used.)

Step Number

Hold

Advance

Standby Time (displays remaining time)

Pattern Elapsing Time

Pattern Execution Count

Operation Value
(heating)

(Control Valve Control)

(Heating/Cooling Control)

Operation Value
(Cooling)

Operation Value

Valve Opening

Operation Value

Time

Time

Number of times

Measured
value

PV/SP

The process value is displayed on the No.1 display and the set
point is displayed on the No.2 display.

When the multi-SP function is in use, the value of whichever is
set, set point 0 or 1, is linked.

Remote SP Monitor

Monitors remote SP in the local SP mode.

Set Point During SP Ramp

Monitors the set point when the SP ramp function is used.

J

PROTECT MODE

Press twice
for 1 s min.

Security

Key protect

To level 0

Press twice
for 1 s min.

RUN/RST

RUN/RST

0

Security

Any mode marked with “X” in the following table is not displayed
on the menu when this parameter is set to “0” to “3.”

Mode

Set value

0

1

2

3

4

Calibration

---

x

x

x

x

Option

---

---

x

x

x

Expansion

---

---

x

x

x

Setup

---

---

x

x

x

Level 2

---

---

---

x

x

Level 1, 0

---

---

---

---

x

The Unit will be in only level 0 mode and the menu will not be avail-
able when this parameter is set to “4” to “6.”

Only the “PV/SP” parameter in the level 0 mode can be used when
this parameter is set to “5.”

Only the “PV/SP” parameter in the level 0 mode can be used
when this parameter is set to “6.”

Key Protect

Invalidate the automatic, manual, run, and reset functions.

J

MANUAL MODE

A/M

Press both simultaneously for more than 1 second
to switch between auto or manual.

Summary of Contents for E5CK-AA1-500 AC100-240

Page 1: ...H High accuracy 100 ms sampling for analog input H Conforms to international EMC and safety standards H 24V AC DC type also available H 3 year warranty RC Ordering Information Order control output boa...

Page 2: ...DE0106 part 100 E5CK T 1 E53 COV07 Software For setup and monitoring requires optional computer communications board All 1 SYS CONFIG V2 0 Temperature Ranges Platinum Resistance Thermometer Input swit...

Page 3: ...units of 0 1 FS Integral reset time I 0 to 3 999 s in units of 1 s Derivative rate time D 0 to 3 999 s in units of 1 s Control period 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in unit...

Page 4: ...contact discharge level 2 8kV air discharge level 3 Immunity RF interference ENV50140 10V m amplitude modulated 80 MHz to 1 GHz level 3 10 V m pulse modulated 900 MHz Immunity Conducted Disturbance E...

Page 5: ...rd model set up the output boards for control outputs 1 and 2 before mounting the Controller 2 On a position proportional model the relay output board is already set so this setup operation is unneces...

Page 6: ...74 Dimensions Unit mm inch J E5CK T 60 2 36 min Panel Cutouts 65 2 56 min 48 1 89 58 2 28 13 3 0 52 100 3 94 53L x 53W 44 8 X 44 8 J ACCESSORIES ORDER SEPARATELY Terminal Cover E53 COV07 44 3 1 74 44...

Page 7: ...arefully pull the internal mechanism from the housing Refer to the drawing below J SETTING UP THE OUTPUT BOARD 1 Two rectangular holes are provided on the power board right side of Controller Fit the...

Page 8: ...cm Adapter Panel Watertight packing Input Jumper Setting Note The jumper is factory set to TC S PT temperature input Set the jumper to temperature voltage or current input according to the sensor con...

Page 9: ...s from external noise Solderless terminals are recommended when wiring the Controller Tighten the terminal screws using a torque no greater than 0 78 N S m or 8 kgf S cm max Be careful not to tighten...

Page 10: ...eter inputs set the inputs to a common position TC PT as the temperature input Control Output Terminal numbers 11 and 12 are for control output 1 OUT1 The five output types and internal equalizing cir...

Page 11: ...8 7 6 13 14 11 12 3 2 Relay specifications are as follows SPST NO 250 VAC 1 A Option Terminal numbers 1 13 and 14 are valid only when the option board is set in the Controller The following four conn...

Page 12: ...ay key sp0 0 4 Set the target value to 50 Target value Display key 50 sp0 Step number display 5 Press the Display Key to shift to the display for the time of Step 0 Time parameter for step 0 Step time...

Page 13: ...C 199 9 to 999 9 F Platinum resistance 1 Pt100 199 9 to 650 0 C 199 9 to 999 9 F thermometer 2 K1 200 to 1 300 C 300 to 2 300 F Thermocouple 3 K2 0 0 to 500 0 C 0 0 to 900 0 F 4 J1 100 to 850 C 100 t...

Page 14: ...and 2 and auxiliary outputs 1 and 2 The assignment destination of each output function is restricted Refer to the tables provided under the headings Standard Models and Position Proportionate Models...

Page 15: ...ce deviation X SP ON OFF X SP ON OFF 7 Lower limit alarm with standby sequence deviation X SP ON OFF X SP ON OFF 8 Absolute value upper limit alarm X 0 ON OFF 0 X ON OFF 9 Absolute value lower limit a...

Page 16: ...e alarm 1 to 3 open in alarm parameters setup mode Factory setting is close in alarm n o J PARAMETER OPERATION LIST Switching to modes other than manual or protect mode is carried out using the mode s...

Page 17: ...AT auto tuning set up the control period change PID parameters and set alarm values Level 2 Mode This is the auxiliary mode for adjusting control In this mode you can set the parameters for limiting...

Page 18: ...tors remote SP in the local SP mode Set Point During SP Ramp Monitors the set point when the SP ramp function is used J PROTECT MODE Press twice for 1 s min Security Key protect To level 0 Press twice...

Page 19: ...arameter of the Controller in standard control is 0 Hysteresis Heat Available when the Controller is in ON OFF control For heating cooling control Hysteresis Cool Available when the Controller is in O...

Page 20: ...ut Shift Lower Limit Available if the input type is a thermocouple or platinum resistance thermometer See Input Shift For models E5AK EK T only Open Close hysteresis Standby time Input Shift Temperatu...

Page 21: ...are used J OPTION MODE Event Input Assignment 1 Available for the event input function Event Input Assignment 2 Available for the event input function For models E5AK E5EK T only Event Input Assignme...

Page 22: ...t value step 0 time step 1 target value and step 1 time The step target value can be set within a range between the lower and upper target value limits The default value is zero The step time can be s...

Page 23: ...p 0 Set the ON OFF timing with the timing signal 1 2 ON time and time signal 1 2 OFF time parameters in Program mode ON Conditions If the ON time is shorter than the OFF time the signal will be reset...

Page 24: ...mal the probable cause may be external noise affecting the control system Check for external noise Operation at Error Control output functions turn OFF 2 mA max at 4 to 20 mA output and output equival...

Page 25: ...ol continues allowing normal operation Motor Calibration Error Displayed on the No 2 Display Meaning Motor calibration has ended with an error Action First correctly connect the wiring for the potenti...

Page 26: ...Unit must be approximately 0 78 N S m or 8 kgf S cm Use the following type of solderless terminals for M3 5 screws 7 2 mm max 7 2 mm max J OPERATION The alarm outputs of a model with an alarm functio...

Page 27: ...Model G3PA G3PB G3NH G3NA G3NE G3B Appear ance SSRs connected in parallel E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 5 pcs E5CK T 2 pcs E5AK E5EK T 2 pcs E5CK T 1 piece...