Input type:
Pt100
(–200.0 - 850.0˚C)
Control method: PID control
Output:
Pulse voltage output
Control period:
0.5 sec
Alarm 1:
Absolute-value
upper-limit alarm
200.0˚C
E5AR-TQ4B 100 to 240 V AC
Examples of typical settings
M
Present value / set point
Program No. Segment No.
1. Turn on power
Turn on power
25.0
0
.
0
l
.
0
l
.
0
l
.
1
l
.
3
i1-t
2
l
.
0
l.
0
i1-t
0
l
.
1
mode
0
l
.
1
o1-t
0
l
.
3
alt1
8
01
.
01
Operation Level
Hold down for at least 3 seconds to make display 3
show
l
.
0
(input default setting level).
(For multi-point input types, the control of all channels stops.)
Control stops
Input Default Setting Level
Input 1 type
2
: K(1)-200.0 - 1300.0˚C
Input type
appears
2. Set input type
Input Default Setting Level
UD
Use the
UD
keys
to change the
input type
Input 1 type
2
→
0
: Pt100(1) -200.0 - 850.0˚C
1. See the input
allocation list
(p. 9)
* Check the input
type switch.
Press for less than 1 second to make display 3
show
l.1
(control default setting level)
3. Set control mode
Control Default Setting Level
Check the control
mode
Check the
Output 1 type
Control mode
0
:Standard PID control
Output 1 type
0
:Pulse voltage output
2. See the output
type list (p.9)
* :means
press the key
repeatedly until
the desired
setting data
appears.
Press for less than 1 second to make display 3
show
l
.
3
(alarm setting level).
Alarm Setting Level
4. Set alarm type
Use the
UD
keys
to change the
alarm type
Alarm type 1
2
→
8
: Absolute-value
upper-limit alarm
3. See the
alarm type
list (p. 9)
Hold down for at least 1 second to return to the
operation level.
SSR
COM
SUB1
SUB2
OUT1
IN1
Temperature sensor:
Pt100
Control object
Voltage output: 12 V DC
Alarm 1
7
Program :
SP
(˚C)
0.0
Segment 2
Segment 3
Segment 4
Time (Hour: Minute)
Program 1