Display Selection
6-4
The screen configuration of the main screen can be selected from 4 types.
Response time can be changed.
Detection becomes more stable as increasing response time.
Response Time
6-1
The output logic (N.O. or N.C.) of output 1 or output 2 can be switched.
The logic of output 2 can be changed only when the output 2 function is
set to [Out2 Single].
Output 1 Mode
6-2
The timer operation of the output can be set.
Timer Mode
6-3
Note 1. Display's luminance decreases as the sensor is used for a long period.
*1. If the ON time < the timer time, output is not turned ON.
*2. If the OFF time < the timer time, output is not turned OFF.
*3. Even if the condition of switching OFF to ON is satisfied while output
is effective, it is ignored.
Display reverse: disabled
Display reverse: enabled
ON
OFF
On delay
ON
OFF
T
Off Delay
ON
OFF
One Shot
ON
OFF
T
T
T
*1
*3
T
Display Reverse
6-5
By enabling display reverse, display is rotated by 180° and the [UP]
button and [DOWN] button are switched.
However, the main screen and the menu setting screen are switched by
the button beside the print, "MODE 3sec," regardless of valid or invalid
of display reverse.
Off
On Delay
Off delay
One shot
The timer function is not used.
Output ON is retarded after the object is detected.
Output ON is held if the detection time is too short for PLC to detect the object.
Output is held for a certain period of time even if the object size varies.
Display Brightness
6-6
Display brightness
Normal
Dark
The brightness of the OLED display decreases after not operated
for a certain time (60s).
The OLED display is turned OFF perfectly after not operated for a
certain time (15s).
Keep Function
6-7
Note 1. If background reference teaching (normal) is executed (when
output 1 mode = [Window FGS], keeping is disabled on output 1 only.
Note 2. If background reference teaching (sensitive) is executed (when
output 1 mode = [Dist + Int]), keeping is disabled.
The output when receiving light intensity is not sufficient or detection
has not been determined yet can be set.
*1. These are the factory settings.
If mutual interference between sensors is not improved even after
changing the channel setting, consider installation of a light
baffle or changing of sensor installation.
Keep
Function
Off
On
Output OFF
The detected value directly before the sensor judges as
impossible to detect is saved and output.
Output ON
Mutual Interference Prevention Function
6-8
Influence of mutual interference between sensors can be reduced by
changing the channel setting to change the interval of emitting pulse.
If mounting more than one sensor close to each other, interference
might occur between those sensors. So, set them to mutually different
channels (up to 4 sensors).
Response time varies depending on the channel configured.
Teaching Selection
6-9
Teaching executed when pressing and holding the teaching button
(longer than 1s and shorter than 5s) can be switched.
"4 Teaching" ( page 5 to 6)
Background Reference Teaching Selection
6-10
Normal mode and Sensitive mode for background reference teaching
can be switched."4 Teaching" ( page 5 to 6)
Standard
Simple
Bar
ON/OFF
Displays the detected value, threshold value, I/O
state, and setting state.
This is the screen configuration of factory settings.
Displays the detected value only.
Displays the detected value as a bar and the
output as an icon. The bar indicates conformity
in a range of 0-100 when the output mode is
"Di Intensity". In the other modes, it
indicates the detecting distance between the
upper and lower limits.
Displays the I/O state only.
Item
Description
Display
DOWN
[DOWN]button
UP
[UP]button
T = timer time
Detecting
state ([Off])
10
*2
Output
Channel 1 *1
Channel 2
Channel 3
Channel 4
1.5ms
2ms
1.7ms
1.8ms
10ms
13ms
11ms
12ms
50ms
65ms
55ms
60ms
Channel
Response time
Timer mode
Description on function
Description
N.O. setting
N.C. setting
1.5ms
10ms
50ms *1