![background image](http://html1.mh-extra.com/html/omron/e3as-hl150-series/e3as-hl150-series_instruction-sheet_740996012.webp)
Laser OFF / Teaching / Zero reset selectable
For the applied voltage, refer to "2-1 Input/Output Circuit Diagram"( page 2). For the input time, refer to "3-3 External Input"( page 3).
Reversed power polarity protection, Output short-circuit protection, and Output reverse polarity protection
OLED Display(White), Power/Communication indicator (Green), Operation indicator (Orange)
1.5 ms / 10 ms / 50 ms selectable
4 units max. (when using the mutual interference prevention function)
Operating: -10 to +50℃ (with no icing or condensation) Storage: -25 to +70℃ (with no icing or condensation)
Operating: 35 to 85%RH, Storage: 35〜95%RH (with no condensation)
20 MΩ min. at 500 VDC
1,000 VAC at 50 / 60 Hz for 1 minute
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
500 m/s
2
for 3 times each in X, Y, and Z directions
IP67 (IEC60529), IP69K (ISO20653)
Pre-wired type: 48.6×30.4×15.5 mm, Connector type: 47.1×28.9×15.5 mm
SUS316L
Polyamide 11 (PA11)
Methacrylic resin (PMMA) (Lens cover: Antifouling coating)
Ver1.1
COM3: 230.4 kbps, COM2: 38.4 kbps
PD size: 4 byte, OD size: 1 byte (M-sequence type: TYPE̲2̲V)
COM3: 1.2 ms, COM2: 3.5 ms
Spot size (reference value)*2
Light source (wavelength)
Power supply voltage
Consumption current
35 to 500 mm
Receiver surface illuminance:
Incandescent lamp: 20,000 lx max., Sunlight: 25,000 lx max. at distance of 250 mm
Incandescent lamp: 5,000 lx max., Sunlight: 10,000 lx max. at distance of 500 mm
Receiver surface illuminance:
Incandescent lamp: 8,000 lx max., Sunlight: 16,000 lx max.
35 to 150 mm
Ratings and Specifications
8
External input
Protection circuits
Indicator
Response time
Mutual interference prevention
Ambient illumination
Ambient temperature
Ambient humidity
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Enclosure ratings
Dimensions
Material
Conformity standards
Control output
Sensing distance
Standard detectable
difference*1
Communication
specifications
Case
E3AS-HL500MN□ series
E3AS-HL500MD□ series
E3AS-HL500MT□ series
2.5×1.5 mm at distance of 500 mm 18×1.5 mm at distance of 500 mm
UL Certification, CE Marking, RCM, EAC, IEC 60825-1:2014 (Laser Class 1), FDA (Laser Class 1), Ecolab, RoHs2, WEEE2
2.5×1.3 mm at distance of 150 mm 8×1.3 mm at distance of 150 mm
E3AS-HL500LMN□ series
E3AS-HL500LMD□ series
E3AS-HL500LMT□ series
E3AS-HL150MN□ series
E3AS-HL150MD□ series
E3AS-HL150MT□ series
E3AS-HL150LMN□ series
E3AS-HL150LMD□ series
E3AS-HL150LMT□ series
NPN output
PNP output/COM2
PNP output/COM3
Model
Triangulation
Sensing method
Indicator
Lens cover and Display
IO-Link specification
Baud rate
Data length
Minimum cycle time
■Model standard
Triangulation
500 mm
150 mm
Spot
Line
Red
Metal
NPN open collector
PNP open collector/COM2
PNP open collector/COM3
HL
500
150
Blank
L
Blank
M
N
D
T
①
Mark
②
③
④
⑤
⑥
Sensing method
Specification
Sensing distance
Emission spot shape
Light source
Case material
Output method
E 3 A S-H L □ □ □ M □ □ □ □
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Note: 1.Altitude: Up to 2000m, Pollution degree: 3, Enclosure type: Type1.
*1. Measured with OMRON's standard workpiece (White ceramic).
*2. Defined by D4σ method at the maximum sensing distance. Detection may be influenced if there is light leakage outside the defined region and the
surroundings of the target object have a high reflectance in comparison to the target object. Also, when detecting a workpiece that is smaller than the spot
size, a correct value may not be obtained.
Pre-wired
Pre-wired M12 Smartclick Connector
Pre-wired M8 Connector
M8 Connctor
Special specification
M8 Connector
2 m+150/-0 mm(Pre-wired)
5 m+150/-0 mm(Pre-wired)
0.3 m+60/-0 mm(Pre-wired Connector)
Blank
‐M1TJ
‐M3J
M3
alphanumerical character
Blank
2M
5M
0.3M
⑦
⑧
⑨
Connection method
Optional suffix
Code length
Suitability for Use
t
OMRON Corporation shall not be responsible for conformity with any standards, codes or
regulations which apply to the combination of the Product in the Buyer’s application or use of
the Product. At Buyer’s request, Omron will provide applicable third party certification
documents identifying ratings and limitations of use which apply to the Product. This
information by itself is not sufficient for a complete determination of the suitability of the
Product in combination with the end product, machine, system, or other application or use.
Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application
responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE
OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
D
OMRON Corporation
Industrial Automation Company
Contact: www.ia.omron.com
Kyoto, JAPAN
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Regional Headquarters
Load power supply voltage 30 VDC max.(Class2), the total load current of the two outputs is 100 mA max.
Residual voltage(Load current 10 mA max.: 1 VDC max., Load current 10 to 100 mA: 2 VDC max.)
Open collector output type (Depends on the NPN/PNP output type) N.O.(Normally Open) / N.C.(Normally Close) selectable
Red laser (660 nm)
10 to 30 VDC, (including ripple (p-p) 10%), Class2
100 mA max.
35 to 180 mm:9 mm
180 to 300 mm:18 mm
300 to 400 mm:30 mm
400 to 500 mm:45 mm
at 10 msec
35.0 to 50.0 mm:1 mm
50.0 to 100.0 mm:2 mm
100.0 to 150.0 mm:4 mm
at 10 msec