CJ2H-CPU6

@

-EIP

Symbols 
(Variables) 

Type of Symbols

Local symbols: Can be used only within a single task in the PLC.

Global symbols: Can be used in all tasks in the PLC.

Network symbols (tags): I/O memory in the CPU Unit can be externally accessed using symbols, depending 
on parameter settings.

Data Type of Symbols

BOOL (bit)

UINT (one-word unsigned binary)

UDINT (two-word unsigned binary)

ULINT (four-word unsigned binary)

INT (one-word signed binary)

DINT (two-word signed binary)

LINT (four-word signed binary)

UINT BCD (one-word unsigned BCD) 

*

1

UDINT BCD (two-word unsigned BCD) 

*

1

ULINT BCD (four-word unsigned BCD) 

*

1

REAL (two-word floating-point)

LREAL (four-word floating-point)

CHANNEL (word) 

*

1

NUMBER (constant or number) 

*

1

WORD (one-word hexadecimal)

DWORD (two-word hexadecimal)

LWORD (four-word hexadecimal)

STRING (1 to 255 ASCII characters)

TIMER (timer) 

*

2

COUNTER (counter) 

*

2

*1.

Cannot be used in Function blocks

*2.

Can be used only in Function blocks

Maximum Size of Symbol

32k words

Array Symbols (Array Variables)

One-dimensional arrays

Number of Array Elements

32,000 elements max.

Number of Registrable Network 
Symbols (Tags)

20,000 max.

Length of Network Symbol (Tag) 
Name

255 bytes max.

Encoding of Network Symbols 
(Tags)

UTF-8

Data Tracing

Memory Capacity

8,000 words

16,000 words

32,000 words

(Up to 32k words 

×

 25 banks when EM is specified in CX-Programmer) 

Number of Samplings

Bits = 31, one-word data =16, two-word data = 8, four-word data = 4

Sampling Cycle

1 to 2,550 ms (Unit: 1 ms)

Trigger Conditions

ON/OFF of specified bit
Data comparison of specified word
Data size: 1 word, 2 words, 4 words
Comparison Method: Equals (=), Greater Than (>), Greater Than or Equals (

), Less Than (<), Less Than or 

Equals (

), Not Equal (

)

Delay Value

32,768 to +32,767 ms

File Memory

Memory Card (128, 256, or 512 Mbytes) (Use the Memory Cards provided by OMRON.) 
EM file memory (Part of the EM Area can be converted for use as file memory.) 

Source/
Comment 
Memory

Function block program 
memory, comment file, program 
index file, symbol tables

Capacity: 3.5 Mbytes

Items

CJ2H-

CPU64-EIP

CPU65-EIP

CPU66-EIP

CPU67-EIP

CPU68-EIP

Summary of Contents for CJ2H-CPU68-EIP -

Page 1: ...P as a standard feature for high speed high capacity Ethernet based networking Features High speed high capacity EtherNet IP is built into every model The CIP communications protocol is supported for...

Page 2: ...cessories come with CPU Unit Product name Specifications Current consumption A Model Standards I O capacity Mountable Units Expansion Racks Program capacity Data memory capacity LD instruction executi...

Page 3: ...0 m or less Pollution Degree 2 or less Conforms to JIS B3502 and IEC 61131 2 Noise Immunity 2 kV on power supply line Conforms to IEC 61000 4 4 Overvoltage Category Category II Conforms to JIS B3502 a...

Page 4: ...xiliary Area Read only 31 744 bits 1 984 words 7 168 bits 448 words Words A0 to A447 24 576 bits 1 536 words Words A10000 to A11535 Read write 16 384 bits 1 024 words in words A448 to A1471 Temporary...

Page 5: ...blocks Maximum Size of Symbol 32k words Array Symbols Array Variables One dimensional arrays Number of Array Elements 32 000 elements max Number of Registrable Network Symbols Tags 20 000 max Length...

Page 6: ...00 ms Unit 0 5 ms Can be set for each connection Data will be refreshed at the set interval regardless of the number of nodes Permissible Communications Band 6 000 pps 1 Number of Tag Sets 256 Type of...

Page 7: ...d to enable detecting shorter input pulses Load OFF Function All of the outputs on Basic I O Units can be turned OFF when an error occurs in RUN or MONITOR mode Basic I O Unit Status Monitoring Alarm...

Page 8: ...when operating mode was last changed to RUN mode or MONITOR mode is stored Operation Stop Time Storage The last time a fatal error occurred or the last time the operating mode was changed to PROGRAM...

Page 9: ...ror Detection This function detects an error when the model of a Special I O Unit in the registered I O tables does not agree with the model of Unit that is actually mounted Fatal Error Detection Memo...

Page 10: ...Network Communications Instruction to send required FINS commands to a computer connected via a Host Link Remote Programming and Monitoring Host Link communications can be used for remote programming...

Page 11: ...Programming Console cannot be used with a CJ2H CPU Unit Device Type Setting The unit version does not affect the setting made for the device type on the CX Programmer Select the device type as shown i...

Page 12: ...No protocol or Peripheral Bus Pin No Signal Name Direction 1 FG Protection earth 2 SD TXD Send data Output 3 RD RXD Receive data Input 4 RS RTS Request to send Output 5 CS CTS Clear to send Input 6 5...

Page 13: ...smission Paths Star Baud Rate 100 Mbps 100Base TX Transmission Media Shielded twisted pair STP cable Categories 5 5e Transmission Distance 100 m between hub and node Number of Cascade Connections No r...

Page 14: ...eference Manual Information on communications for CS CJ CP series CPU Units and NSJ series Controllers Describes C mode commands and FINS commands Refer to this manual for a detailed description of co...

Page 15: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Reviews: