Unit Versions

Function Support by Unit Version

Unit Version 1.1 or Later

CX-Programmer version 8.02 or higher must be used to enable using the functions added for unit version 1.1.

Note:

User programs that use functions of CJ2H CPU Units with unit version 1.1 or later cannot be used with CJ2H CPU Units with unit version 
1.0 or earlier. If an attempt is made to transfer a program that uses any of these functions from the CX-Programmer to a CPU Unit with unit 
version 1.0, an error will be displayed and it will not be possible to download to the CPU Unit. If a program file (extension: .OBJ) that uses 
any of these functions is transferred to a CPU Unit with unit version 1.0, a program error will occur when operation starts or when the function 
starts and operation of the CPU Unit will stop.

Self-
diagnosis 
and 
Restoration 
(Continued 
from 
previous 
page)

Fatal Error 
Detection 
(Continued from 
previous page)

System FALS Error Detection 
(User-defined Fatal Error)

This function generates a fatal (FALS) error when the user-defined conditions are met in 
program. 

Version Error Detection

This function detects an error when a user program includes a function that is not supported 
by the current unit version.

Memory Card Transfer Error 
Detection

This function detects an error when the automatic file transfer from Memory Card fails at 
startup.

Memory Self-restoration Function 

This function performs a parity check on the user program area and self-restoration data. 

Maintenance

Simple Backup Function

This function collectively backs up the data in CPU Unit (user programs, parameters, and I/O 
memory) and internal backup data in the I/O Units.

Unsolicited Communications

A function that allows the PLC to use Network Communications Instruction to send required 
FINS commands to a computer connected via a Host Link

Remote Programming and Monitoring

Host Link communications can be used for remote programming and remote monitoring 
through a Controller Link, Ethernet, DeviceNet, or SYSMAC LINK Network. Communications 
across network layers can be performed.
Controller Link or Ethernet: 8 layers
DeviceNet or SYSMAC LINK: 3 layers

Automatic Online Connection via 
Network

Direct 
Serial 
Connection

This function enables automatically connecting to the PLC online when the CX-Programmer 
is directly connected by a serial connection (peripheral (USB) port or serial port).

Via 
Networks

This function enables connecting the CX-Programmer online to a PLC that is connected via an 
EtherNet/IP network.

Security

Read Protection using Password

This function protects reading and displaying programs and tasks using passwords.
Write protection: Set using the DIP switch.
Read protection: Set a password using the CX-Programmer.

FINS Write Protection

This function prohibits writing by using FINS commands sent over the network.

Unit Name Function

This function allows the users to give any names to the Units. Names are verified at online 
connection to prevent wrong connection

Hardware ID Using Lot Numbers

This function sets operation protection by identifying hardware using the user programs 
according to lot numbers stored in the Auxiliary Area.

Units

Models

Unit version

CJ2H CPU Units

CJ2H-CPU6

@

-EIP

CPU: Unit version 1.0
EIP: Unit version 2.0

CPU: Unit version 1.1
EIP: Unit version 2.0

Unit

CJ2H CPU Unit

Model

CJ2H-CPU6

@

-EIP

Unit version

Item

Unit version 1.1

Unit version 1.0

High-speed interrupt function
  Decreased overhead time for interrupt tasks
  Minimum interval setting of 0.1 ms for Scheduled Interrupt Task

Supported.

Not supported.

Changing the minimum cycle time setting in MONITOR mode

Supported.

Not supported.

Function

Description

Summary of Contents for CJ2H-CPU68-EIP -

Page 1: ...P as a standard feature for high speed high capacity Ethernet based networking Features High speed high capacity EtherNet IP is built into every model The CIP communications protocol is supported for...

Page 2: ...cessories come with CPU Unit Product name Specifications Current consumption A Model Standards I O capacity Mountable Units Expansion Racks Program capacity Data memory capacity LD instruction executi...

Page 3: ...0 m or less Pollution Degree 2 or less Conforms to JIS B3502 and IEC 61131 2 Noise Immunity 2 kV on power supply line Conforms to IEC 61000 4 4 Overvoltage Category Category II Conforms to JIS B3502 a...

Page 4: ...xiliary Area Read only 31 744 bits 1 984 words 7 168 bits 448 words Words A0 to A447 24 576 bits 1 536 words Words A10000 to A11535 Read write 16 384 bits 1 024 words in words A448 to A1471 Temporary...

Page 5: ...blocks Maximum Size of Symbol 32k words Array Symbols Array Variables One dimensional arrays Number of Array Elements 32 000 elements max Number of Registrable Network Symbols Tags 20 000 max Length...

Page 6: ...00 ms Unit 0 5 ms Can be set for each connection Data will be refreshed at the set interval regardless of the number of nodes Permissible Communications Band 6 000 pps 1 Number of Tag Sets 256 Type of...

Page 7: ...d to enable detecting shorter input pulses Load OFF Function All of the outputs on Basic I O Units can be turned OFF when an error occurs in RUN or MONITOR mode Basic I O Unit Status Monitoring Alarm...

Page 8: ...when operating mode was last changed to RUN mode or MONITOR mode is stored Operation Stop Time Storage The last time a fatal error occurred or the last time the operating mode was changed to PROGRAM...

Page 9: ...ror Detection This function detects an error when the model of a Special I O Unit in the registered I O tables does not agree with the model of Unit that is actually mounted Fatal Error Detection Memo...

Page 10: ...Network Communications Instruction to send required FINS commands to a computer connected via a Host Link Remote Programming and Monitoring Host Link communications can be used for remote programming...

Page 11: ...Programming Console cannot be used with a CJ2H CPU Unit Device Type Setting The unit version does not affect the setting made for the device type on the CX Programmer Select the device type as shown i...

Page 12: ...No protocol or Peripheral Bus Pin No Signal Name Direction 1 FG Protection earth 2 SD TXD Send data Output 3 RD RXD Receive data Input 4 RS RTS Request to send Output 5 CS CTS Clear to send Input 6 5...

Page 13: ...smission Paths Star Baud Rate 100 Mbps 100Base TX Transmission Media Shielded twisted pair STP cable Categories 5 5e Transmission Distance 100 m between hub and node Number of Cascade Connections No r...

Page 14: ...eference Manual Information on communications for CS CJ CP series CPU Units and NSJ series Controllers Describes C mode commands and FINS commands Refer to this manual for a detailed description of co...

Page 15: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Reviews: