Omron CJ2H-CPU68-EIP - Datasheet Download Page 12

CJ2H-CPU6

@

-EIP

12

External Interface

A CJ2H CPU Unit (CJ2H-CPU6

@

-EIP) provides three communications ports for external interfaces: a peripheral (USB) port, a sirial port and an 

EtherNet/IP port.

Peripheral (USB) Port

Serial Port

*

Baud rates for the RS-232C are specified only up to 19.2 kbps. The CJ Series supports serial communications from 38.4 kbps to 115.2 kbps, 
but some computers cannot support these speeds. Lower the baud rate if necessary.

Note:

Do not use the 5-V power from pin 6 of the RS-232C port on the CPU Unit for anything but the NT-AL001-E Link Adapter. The external 
device or the CPU Unit may be damaged. 

Item

Specification

Baud Rate

12 Mbps max.

Transmission Distance

5 m max.

Interface

USB 2.0-compliant B-type connector

Protocol

Peripheral Bus

Item

Specification

Communications method

Half duplex

Synchronization

Start-stop

Baud rate

0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4/57.6/115.2 kbps 

*

Transmission distance

15 m max.

Interface

EIA RS-232C

Protocol

Host Link, NT Link, 1:N, No-protocol, or Peripheral Bus

Pin No.

Signal

Name

Direction

1

FG

Protection earth

2

SD (TXD)

Send data

Output

3

RD (RXD)

Receive data

Input

4

RS (RTS)

Request to send

Output

5

CS (CTS)

Clear to send

Input

6

5 V

Power supply

7

DR (DSR)

Data set ready

Input

8

ER (DTR)

Data terminal ready

Output

9

SG (0 V)

Signal ground

Connector hood

FG

Protection earth

Battery Compartment

LED Indicators

DIP Switch

(inside the battery compartment)

Memory Card Indicators 

Indicates the Memory Card status 
(access and power supply).

Peripheral (USB) Port

Connected to Programming Devices, 
such as the CX-Programmer

Serial Port

Connected to Programming Devices, Host 
Computers, general-purpose external devices, 
Programmable Terminals, and other devices.

EtherNet/IP Port

Connected to the information management
system such as Host Computer

Simple Backup/Memory Card 
Power Supply Switch

Used to back up Memory 
Card data or turn OFF the
power when removing the 
Memory Card. 
Also, press the Memory Card 
Power Supply Switch to 
perform an easy backup 
operation.

Memory Card Connector

Connects the Memory Card 
to the CPU Unit.

Memory Card Eject Button 

Press the eject button to 
remove the Memory Card 
from the CPU Unit.

5

1

9

6

Summary of Contents for CJ2H-CPU68-EIP -

Page 1: ...P as a standard feature for high speed high capacity Ethernet based networking Features High speed high capacity EtherNet IP is built into every model The CIP communications protocol is supported for...

Page 2: ...cessories come with CPU Unit Product name Specifications Current consumption A Model Standards I O capacity Mountable Units Expansion Racks Program capacity Data memory capacity LD instruction executi...

Page 3: ...0 m or less Pollution Degree 2 or less Conforms to JIS B3502 and IEC 61131 2 Noise Immunity 2 kV on power supply line Conforms to IEC 61000 4 4 Overvoltage Category Category II Conforms to JIS B3502 a...

Page 4: ...xiliary Area Read only 31 744 bits 1 984 words 7 168 bits 448 words Words A0 to A447 24 576 bits 1 536 words Words A10000 to A11535 Read write 16 384 bits 1 024 words in words A448 to A1471 Temporary...

Page 5: ...blocks Maximum Size of Symbol 32k words Array Symbols Array Variables One dimensional arrays Number of Array Elements 32 000 elements max Number of Registrable Network Symbols Tags 20 000 max Length...

Page 6: ...00 ms Unit 0 5 ms Can be set for each connection Data will be refreshed at the set interval regardless of the number of nodes Permissible Communications Band 6 000 pps 1 Number of Tag Sets 256 Type of...

Page 7: ...d to enable detecting shorter input pulses Load OFF Function All of the outputs on Basic I O Units can be turned OFF when an error occurs in RUN or MONITOR mode Basic I O Unit Status Monitoring Alarm...

Page 8: ...when operating mode was last changed to RUN mode or MONITOR mode is stored Operation Stop Time Storage The last time a fatal error occurred or the last time the operating mode was changed to PROGRAM...

Page 9: ...ror Detection This function detects an error when the model of a Special I O Unit in the registered I O tables does not agree with the model of Unit that is actually mounted Fatal Error Detection Memo...

Page 10: ...Network Communications Instruction to send required FINS commands to a computer connected via a Host Link Remote Programming and Monitoring Host Link communications can be used for remote programming...

Page 11: ...Programming Console cannot be used with a CJ2H CPU Unit Device Type Setting The unit version does not affect the setting made for the device type on the CX Programmer Select the device type as shown i...

Page 12: ...No protocol or Peripheral Bus Pin No Signal Name Direction 1 FG Protection earth 2 SD TXD Send data Output 3 RD RXD Receive data Input 4 RS RTS Request to send Output 5 CS CTS Clear to send Input 6 5...

Page 13: ...smission Paths Star Baud Rate 100 Mbps 100Base TX Transmission Media Shielded twisted pair STP cable Categories 5 5e Transmission Distance 100 m between hub and node Number of Cascade Connections No r...

Page 14: ...eference Manual Information on communications for CS CJ CP series CPU Units and NSJ series Controllers Describes C mode commands and FINS commands Refer to this manual for a detailed description of co...

Page 15: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Reviews: