3 Checking and starting the operation
3-4 Operations using the LCD menu
BU5002R/BU3002R/BU3002RH
89
3
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu
Description
Value
Menu type
Settings Boot Settings
Reboot
Batt.level
Sets the battery level for
reboot.
Reboot battery level:
0 to 100%
(Factory default: 0%)
Advanced
Auto Reboot
Mode
Selects a mode for reboot.
(Note 4)
Auto reboot mode:
Mode A (factory default)
Mode B
Power SW Off
Mode
Switches the operation mode
of the power switch.
Power switch off mode:
UPS shutdown
(factory default),
UPS + PC shutdown
Battery
Settings
Battery Test
Sets the interval of
self-diagnostic test
execution.
Battery test:
Start up/Every 4week
(factory default),
Start up, Every 4 week, Disable
Standard
Batt.life
Counter
Selects whether to notify the
user about the battery’s end
of life.
Battery life counter:
Enabled (factory default), Disabled
Battery
Installation
Set the date when the
battery was replaced.
Battery installation date:
Year, month, day
(Factory default: 1/1/2020)
Max.backupTi
me
☆
Sets the time to stop the
output of the UPS.
Maximum backup time:
Disabled (factory default),
Enabled: 10 to 999 seconds,
Enabled: 1 to 9999 minutes
Advanced
Low Battery
Warning
☆
Sets the level at which a low
battery warning can be
detected.
Low battery warning:
30% (factory default),
Change the level: 0 to 100%
Dry
Contact
BSsignal
ValidRange
☆
Sets the condition for BS
signal reception.
BS signal valid range:
Always enabled (factory default),
Only for backup operation