3 Checking and starting the operation
3-4 Operations using the LCD menu
BU5002R/BU3002R/BU3002RH
87
3
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu
Description
Value
Menu type
Settings Local Settings Calendar
Setting
Sets the calendar
information for the UPS.
Calendar settings: Year, month,
day, hour, minute
Standard
UPS
Installation
Sets the date when the use
of the UPS started.
UPS usage start date: Year, month,
day
(factory default: January 1.2020)
UPS Life
Counter
Sets the operation of the
UPS life counter.
UPS life counter:
Enabled (factory default), Disabled
Menu Type
Selects the menu to be
displayed
. When “Standard”
is selected, only items that
are frequently used are
displayed.
Menu type:
Standard (factory default),
Advanced
In/Out
Settings
O/P Voltage
☆
Sets the output voltage.
Output voltage: 200 V (factory
default), 208 V, 220 V, 230 V, 240
V, 100 V
Standard
Frequency
Range
☆
Switches the frequency
range mode.
Frequency range:
Normal range (factory default),
Wide range
(Note 1)
Advanced
ECO Mode
☆
Switches to the Eco mode.
(Note 2)
Enable, Disable (factory default)