![Omron BU3002R Instruction Manual Download Page 88](http://html1.mh-extra.com/html/omron/bu3002r/bu3002r_instruction-manual_744592088.webp)
3 Checking and starting the operation
3-4 Operations using the LCD menu
BU5002R/BU3002R/BU3002RH
88
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu
Description
Value
Menu type
Settings Boot Settings
Auto Reboot
Selects whether to perform
automatic reboot from power
outage.
Automatic restart:
Enabled (factory default), Disabled
Standard
Cold Start
Selects whether to enable
the “Cold Start” function,
which can start up the UPS
without “AC input”.
Enable, Disable (factory default)
Advanced
Reboot Delay
Time
Sets the delay time for
recovery from a power
outage.
Reboot delay time:
0 to 999 seconds
(Factory default: 9 seconds)
Load
Segments(B)
ON
The time to start the output
of "power supply output"
group B can be delayed.
ON delay: 0 to 9 seconds
ON delay: 0.0 to 0.9 minutes
ON delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
Load
Segments(B)
OFF
The time to stop the output of
"power supply output" group
B can be accelerated.
OFF delay: 0 to 9 seconds
OFF delay: 0.0 to 0.9 minutes
OFF delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
Load
Segments(C)
ON
The time to start the output
of "power supply output"
group C can be delayed.
ON delay: 0 to 9 seconds
ON delay: 0.0 to 0.9 minutes
ON delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)
Load
Segments(C)
OFF
The time to stop the output of
"power supply output" group
C can be accelerated.
OFF delay: 0 to 9 seconds
OFF delay: 0.0 to 0.9 minutes
OFF delay: 0 to 30 minutes
(Factory default: 0 seconds)
(Note 3)