2 Installation and connection
2-3 Connecting the equipment
BU5002R/BU3002R/BU3002RH
43
2
2-3 Connecting the equipment
Caution
Do not connect devices with rated voltage other than
200/208/220/230/240/100 VAC.
⚫
The rated output voltage of the unit is 200/208/220/230/240/100 VAC.
⚫
There is a possibility of a breakdown of the connected device due to
excess voltage.
When using in 100 V output mode, check that the output voltage
is set to 100 V before turning on the power switch.
⚫
When 100 V device is connected during output in 200 V mode, there is a
risk of breakdown of the device or fire.
⚫
The output voltage can be set from the LCD menu by [3. Settings] -
[In/Out Settings] - [O/P Voltage].
⚫
The upper limit of capacity changes in 100 V output mode.
BU5002R:
2500VA/2250W
BU3002R/BU3002RH: 1500VA/1350W
⚫
In 100 V output mode, it is not possible to switch to bypass operation.
⚫
In 100 V output mode, it is not possible to operate in Eco mode
(commercial direct output).
Do not connect devices that cannot be used with the
commercial power supply.
⚫
When the unit
is set to “Eco mode” and a fault occurs on the device,
operation is switched to direct commercial power, and the commercial
power supply is provided to the connected device as it is.
Notes
When the unit is used as a conforming product of UL standards, 100 V
output cannot be used.