3 Checking and starting the operation
3-3 Basic operations including running and stopping the UPS
BU5002R/BU3002R/BU3002RH
81
3
Backup operation is notified with the following status display and intermittent buzzer sound.
Icon
Buzzer
Output
Charge
Description
Solution
Intermittent,
4 second
intervals
ON
OFF
Dischar
ging
The UPS is in
backup operation
due to a power
outage or AC input
error.
If this backup
operation is
continued, the
output stops when
the battery residual
capacity has been
depleted.
Shut down and
stop the
connected
devices that are
in use (carry out
the termination
process).
Charge the
battery.
Intermittent,
1 second
intervals
ON
OFF
Dischar
ging
None
OFF
OFF
Dischar
ging
The residual
capacity of the
battery has been
depleted, so output
has stopped.
Charge the
battery.
The buzzer ON/OFF can be set from the LCD menu by [3.Settings] - [Local
Settings] - [Audible Alarm].
■ Actions after recovery from the power outage
● If the battery power still remains
When power outage or input power fault is solved while power is being output from the
UPS, the output automatically returns to the commercial power supply. Recharging of the
depleted battery starts.
● If the battery has run out
When power outage or input power fault is solved after the battery is depleted and power
output is stopped, the UPS automatically restarts and power output commences again.
Recharging of the depleted battery starts.
When recovery from a power outage is made, by factory default, the UPS
automatically restarts and supplies power. If you do not want to activate the
connected devices, either turn off their switches or disable the automatic start
setting for recovery from a power outage ([3. Settings] - [Boot Settings] - [Auto
Reboot]).