![Omron BU3002R Instruction Manual Download Page 30](http://html1.mh-extra.com/html/omron/bu3002r/bu3002r_instruction-manual_744592030.webp)
2 Installation and connection
2-1 Precautions and notes on installation and connection
BU5002R/BU3002R/BU3002RH
30
2 Installation and connection
2-1 Precautions and notes on installation and
connection
Notes and requests for installing and connecting the unit are listed below. Be sure to read
them and use the unit correctly.
Warning
Do not place the unit on other devices as it is heavy.
⚫
Do not place an expansion battery unit on the unit, or place the unit on an
expansion battery unit.
⚫
There is a risk that an injury could be caused if it falls.
Caution
Remove the battery when moving the unit.
⚫
If not removed, because of the heavy object, there is a risk of injury by
dropping the product, or by the sheer weight of the product.
Do not lift by holding the front panel.
⚫
There is a possibility that the panel comes off, leading to drop of a battery
pack and personal injury.
Notes
Do not connect the AC input plug of this unit into the power output
receptacle or terminal block of this unit during backup operation.
⚫
There is a risk of a breakdown of the unit.
Do not conduct a withstanding voltage test.
⚫
A surge absorber is provided on the power supply input cable, and if a withstanding
voltage test is conducted, the surge absorber may be damaged.
⚫
If conducting an insulation resistance test, perform it in the 250 VDC range.