6 Contact signal functions
6-1 Contact signal functions
6 Using the contact signal functions
6-1 Contact signal functions
Contact Signal
You can develop your unique system based on the following specifications to automate the
process at a power failure. You can perform power-failure processing by allowing the
system to detect the backup signal and also perform system shutdown processing by
allowing the system to detect the Low battery level signal. Also, by inputting the backup
stop signal from the system, you can stop the UPS with a sufficient battery level to prepare
for the next occurrence of a power failure.
6-1-1 Type of Output signals
The UPS has 4 kinds of output signals.
The output circuit consists of an open collector circuit using a photo coupler (a kind of
electronic switch).
Signals
Descriptions
Backup Signal output (BU)
Stays ON during backup operation at a power failure.
Low battery level signal output (BL)
Goes ON when the battery becomes weak during backup operation
at a power failure.
Trouble Signal output (TR)
Goes ON when an internal failure of the UPS occurs or when the
battery life counter expires.
Battery Replacement Signal output (WB)
Goes ON when the test determines that battery replacement is
necessary due to deterioration or when the battery life counter goes
off-scale.
6-1-2 Type of Input signals
The UPS has 2 kinds of input signals.
Signals
Descriptions
Input of the UPS Stop Signal (BS)
When the BS signal is ON (High), the output of the UPS is stopped
after the time period specified in advance has elapsed. (Note 1).
Remote ON/OFF Signal
Remote ON/OFF signals can be used to start and stop the UPS, by
using either an externally connected contact or the ON/OFF status
of the open collector circuit.
When signal is OFF, the UPS will be turned on. When signal is ON,
the UPS will be turned off.
In the factory settings, the UPS stops operation when this is
short-circuited.
In addition, it is necessary to turn on the “Power” switch of UPS to
use this function (Note 2).
Note 1: BS Delay Time:
You can set the amount of time between when the BS signal is received and when the output of
the UPS is stopped (See also "3-5-2 Settings").
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10
seconds from the outside.
Note 2: Connection terminals are at contact signal port pins 6, 7 and the remote ON/OFF port (See
also "3-1-4 Setting Switch").
BA75T/BA100T/BA100R
82
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...