4 Checking the battery
4-1 Checking the battery
■
Manual testing
This test can also be performed manually. Press and hold
the “Buzzer Pause/Test” switch of the UPS for 5 seconds or
longer. When the beeper begins to sound intermittently,
release the Switch.
By performing the self-diagnosis test, backup operation is started automatically.
(Status indicator “
”, No beep sounds.)
After the test is completed, UPS automatically returns to the normal operation.
If the status indicator/battery replacement lamp blinks and the beeper sounds: See also
"3-4 Interpreting beeps and displays".
Additional Information
●
Follow the directions for the solutions described in “3-4-4 Displays and beeps when
there is an equipment failure” and “4-2 Replacing the battery”.
●
The self-diagnosis test can be performed also from attached UPS monitoring software.
For more details, refer to the online help of UPS monitoring software.
4-1-3 Estimated backup time
The backup time varies depending on the capacity of connected devices.
After calculating the total capacity of connected devices, refer to the graph of the backup
time to obtain an estimation of the initial value of the backup time. (This is also applied to
checking the battery.)
1.
Convert the total capacity (power consumption) of the connected devices to watts (W).
For the indication of connected devices, check your computer and the rear of the
display. The indicator can show values in three different ways: volt-amperes (VA),
amperes (A), and watts (W).
Example 1) 100 VAC, 50/60 Hz, 145 W
Indication
Value
Example 2) 100 VAC, 50/60 Hz, 1.8 A
A
A × power factor × 100 = W
Example 3) 100 VAC, 50/60 Hz, 150 VA
VA
VA × power factor × 100 = W
For devices that use the VA or A indication, convert the capacity into W. Multiply the
value indicated on devices by the value in the right table for conversion.
(When the power factor is unknown, enter “1”. The power factor usually ranges
between 0.6 and 1.)
2.
Add the values converted into W to obtain the total capacity of the connected devices.
3.
Calculate the initial value of the backup time for the total capacity of the connected
devices from the graph below.
・
Graph of backup time (graph of initial values for products that have not been used
at 25°C). The backup time becomes shorter than the graph (table) below when
temperature is lower.
・
The smaller the capacity of connected devices becomes, the longer the backup
time becomes.
BA75T/BA100T/BA100R
58
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...