CP TD1 Reference Manual V 1.44
58
5.3
"UST" and "GST" Measurements Using the Guard
Technology
In electrical devices like power transformers there are a lot of insulation gaps,
which have to be checked separately:
• Winding to winding
• Winding to tank & core
• Bushings
A three-winding transformer with the different insulation gaps is shown in figure
5-21. Only one phase is drawn. With a three-phase transformer the equivalent
circuit diagram is very similar, because normally the phases of the high-voltage
(H), the low-voltage (L) and the tertiary (T) windings are connected internally in
y or delta. This way only the sum of all three phases can be measured, the single
phases can not be measured separately.
Figure 5-21
Three-phase transformer with winding capacitances
H
High-Voltage
winding
C H
Cap. H to Ground
C H-L Cap. H to
L
L
Low-Voltage winding C L
Cap. L to Ground
C L-T Cap. L to T
Core
T
L
H
C
H
C
H-L
C
L-T
C
H-T
C
T
C
L
Tank
G
Summary of Contents for CP TD1
Page 1: ...CP TD1 Reference Manual...
Page 14: ...CP TD1 Reference Manual V 1 44 14...
Page 20: ...CP TD1 Reference Manual V 1 44 20...
Page 32: ...CP TD1 Reference Manual V 1 44 32...
Page 38: ...CP TD1 Reference Manual V 1 44 38...
Page 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Page 114: ...CP TD1 Reference Manual V 1 44 114...
Page 128: ...CP TD1 Reference Manual V 1 44 128...
Page 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Page 184: ...CP TD1 Reference Manual V 1 44 184...
Page 186: ...CP TD1 Reference Manual V 1 44 186...