Technical Data
121
Power factor PF (cos
ϕ
)
Phase angle
ϕ
Impedance Z
Inductance Lx (equivalent serial circuit)
Quality factor QF
Power P, Q, S (selective)
Range
Resolution Typ. accuracy
Conditions
0 ... 10%
(capacitive)
5 digits
error < 0.1% of reading
+ 0.005%
1
1. Reduced accuracy of PF at mains frequency or its harmonics. Mains frequency suppression
available by precisely selecting a mains frequency of *50Hz or *60Hz in the "Hz" column.
f = 45 ... 70Hz,
I < 8mA,
Vtest = 300V ... 10kV
0 ... 100%
5 digits
error < 0.5% of reading
+ 0.02%
Vtest = 300V ... 10kV
Range
Resolution Typ. accuracy
Conditions
-90° ... +90°
4 digits
error < 0.01°
Vtest = 300V ... 10kV
Range
Resolution Typ. accuracy
Conditions
1k
Ω
... 1200M
Ω
6 digits
error < 0.5% of
reading
Vtest = 300V ... 10kV
Range
Resolution Typ. accuracy
1H ... 1000kH
6 digits
error < 0.3% of reading
Range
Resolution Typ. accuracy
0 ... 1000
5 digits
error < 0.5% of r 0.2%
> 1000
5 digits
error < 5% of reading
Range
Resolution Typ. accuracy
0 ... 3.6kW
6 digits
error < 0.5% of r 1mW
0 ... 3.6kvar
6 digits
error < 0.5% of r 1mvar
0 ... 3.6kVA
5 digits
error < 0.5% of r 1mVA
Summary of Contents for CP TD1
Page 1: ...CP TD1 Reference Manual...
Page 14: ...CP TD1 Reference Manual V 1 44 14...
Page 20: ...CP TD1 Reference Manual V 1 44 20...
Page 32: ...CP TD1 Reference Manual V 1 44 32...
Page 38: ...CP TD1 Reference Manual V 1 44 38...
Page 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Page 114: ...CP TD1 Reference Manual V 1 44 114...
Page 128: ...CP TD1 Reference Manual V 1 44 128...
Page 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Page 184: ...CP TD1 Reference Manual V 1 44 184...
Page 186: ...CP TD1 Reference Manual V 1 44 186...