Influence of different parameters like water content,
temperature and aging on DF
Figure 5-10 shows the breakdown voltage and the DF in oil, dependent on the
water content [2.3]. With low water content, the breakdown voltage is very
sensitive; with higher water content, the DF is a good indicator.
Figure 5-10
Breakdown voltage and DF in oil, dependent on the water
content
kV/cm
600
500
400
300
200
100
0
60
50
40
30
20
10
0
Br
eakd
own voltag
e
Dissipa
tion fa
ctor
0
20
40
60
80
100
120
140
160
180
200
Water content
mg/kg
tan
δ
ε
d
0
/
00