Operation
23
2.3
CP TD1
Connected to
CP CAL1
Measuring mode = UST-A
When using the
CP CAL1
for calibration, we recommend to take C1 as
reference and to select the calibration frequency in a range between
50 ... 200Hz.
2.4
Calibrating the
CP TD1
Using a Reference Capacitor
By connecting a reference capacitor (e.g., optional device
CP CAL1
) with known
values of capacity Cref and dissipation factor DFref, in mode UST-A the values
Cx and DFx can be measured and then compared to the known reference
values.
CP TD1
CPC 100
Ix
Measurement
PE
Booster
12 kV
IN A
IN B
Grounding terminal
CP CAL1
Serial
C1
C2
C3
Safe area
HV area
Warning:
For using the
CP CAL1
, make sure to apply the same procedure as
described in this Reference Manual.