CP TD1 Reference Manual V 1.44
70
In addition to the previous table , it should be taken into account that overheating
is often caused by bad contacts in the tap selector. In order to find out the reason
for high gas values, further tests have to be performed on the transformer.
Common test methods are:
• Winding resistance measurement
•
O
n-
L
oad
T
ap
C
hanger (OLTC) test
• Turns ratio measurement
• Excitation current measurement
• Measurement of leakage reactance
• Capacitance and Dissipation factor measurement
All the mentioned tests can be done with the
CPC 100
+
CP TD1
. This
instrument is the ideal test and analysis instrument for transformer diagnosis
with these measuring possibilities.
6.2
Capacitance and DF Measurement of Transformer
Windings
General
• The transformer must be taken out of service and completely isolated
from the power system.
• The proper grounding of the transformer tank has to be checked.
• The bushing high-voltage terminals must be isolated from the connection
lines.
• All bushing terminals of one winding group, which means A, B, C (and
Neutral) of high-voltage winding, A, B, C (and Neutral) of low-voltage
Summary of Contents for CP TD1
Page 1: ...CP TD1 Reference Manual...
Page 14: ...CP TD1 Reference Manual V 1 44 14...
Page 20: ...CP TD1 Reference Manual V 1 44 20...
Page 32: ...CP TD1 Reference Manual V 1 44 32...
Page 38: ...CP TD1 Reference Manual V 1 44 38...
Page 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Page 114: ...CP TD1 Reference Manual V 1 44 114...
Page 128: ...CP TD1 Reference Manual V 1 44 128...
Page 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Page 184: ...CP TD1 Reference Manual V 1 44 184...
Page 186: ...CP TD1 Reference Manual V 1 44 186...