9.6.1.2.2
Factory Calibrate
Factory calibration is available for the SS-015 process inputs. Clearing this bit will disable the
factory calibration values.
9.6.1.2.3
Writeable
The writeable bit is cleared, indicating that the sensor values may not be overwritten.
9.6.1.3
Process Input Configuration
Process Input Configuration
7
6
5
4
3
2
1
0
Available
Channel
Scaling
Lock
Sensor Range / Type
0
0*
?
?
(See Below)
9.6.1.3.1
Sensor Range / Type
Sensor
Range/Type
Sensor Input
Type (Range)
Measurement Type
0x01
0-24 mA
0x13
Current (mA)
0x03
0-1.0 Vdc
0x11
Millivolts (mV)
0x09
0-2.0 Vdc
0x11
Millivolts (mV)
9.6.1.3.2
Lock
If set, the user-specified units of measure string (4 character maximum) will be used in place of
the default units of measure.
9.6.1.3.3
Apply Scaling
If set, the user-defined Offset, and Gain values will be used to adjust the sensor reading:
Result = (Raw Reading * Gain) + Offset
9.6.1.3.4
Assigned
The Assigned bit will always read as 0. Refer to the
Smart Sensor Device Interface
documentation for further information.
9.6.1.3.5
Available
The Available bit will always read as 0. Refer to the
Smart Sensor Device Interface
documentation for further information.
9.6.2
Process Device Byte
The Sensor Device field determines the signal types for each of the channel bits.
Process Device Byte
A
(Analog Input)
7 6
5 4 3 2 1 0
Description
1 X
0 0 0 0 0 0
Single Ended
9.6.3
Process Sensor Parameters
There are no Process Sensor Parameters.
3
1
|
P a g e