Parity:
A means of checking the correctness of a character by adding an extra bit to the character and setting
the value based on all the other bits in the character.
•
StopBits:
The number of bits used to indicate the end of the character.
When the user has completed setting the communication parameters for the device, click
Finish
.
6.3
Input Configuration
The SS-015 can accept up to three 0-24 mA, 0-1.0 V
DC
, or 0-2.0 V
DC
process inputs, one digital pulse input, or a mix of
one process and one digital input. These modes are detailed in the below sections.
6.3.1
Process Inputs Interface
To configure the process inputs, follow the steps below:
Figure 6: SYNC interface triple process
Step 1:
Click the
Inputs
configuration tab on SYNC and choose from Single, Dual, or Triple Process in the
Type
dropdown.
Step 2:
Click on each input channel and choose between the mA and mV options from the
Device Range/Type
drop-down. Click
Apply Settings
when done.
6.3.1.1
4-20 mA Device Connection
An input channel configured for 0-24 mA can measure the output of a 4-20 mA device. The Current Loop
interface measures the current into the selected input by converting it to a voltage measurement across
a fixed 49.9-ohm resistor.
Figure 7: 4-20 mA device connection diagram