27 |
M 5 7 5 1
7 Appendix: SP-013 Registers
The following Appendix provides the registers and list index for the Layer N SP-013 Digital Input Smart Probe. This
information is intended to aid users who will be making configurations and adjustments to their Layer N SP-013 Digital
Input Smart Probe through the Command Line Interface or other custom interfaces.
Smart Probe devices share a common platform architecture that provides extensive monitoring and control
capabilities through a set of platform generic registers. These registers may be accessed using I2C based commands
directly to the Smart Probe devices or through a set of Modbus-based registers when using Omega Interface devices.
When powered on or after a device reset each Smart Sensor-based device will enumerate 1 or more sensor instances
which are described by the device-specific Sensor Descriptors which include configuration options, measurement type,
and units of measure for the corresponding sensor values. Additional sensor information is provided in sensor-specific
IPSO object descriptions which include extended measurement type, precision, and tracking of minimum/maximum
readings.
Each enumerated Sensor has a Descriptor Base address location and a Sensor IPSO /Configuration structure address
location based on the sensor mix selected.
Sensor Descriptor Base IPSO/Configuration
Enumerated Sensor
Digital
Mixed Mode
0
0x0060 (0xf030)
0x08a8 (0xf454)
DIN, RATE, WIDTH, DUTY_CYCLE,
or COUNT
DIN, RATE, WIDTH, DUTY_CYCLE,
OR COUNT
1
0x0068 (0xf034)
0x09a8 (0xf4d4)
DIO
Process 0
2
0x0070 (0xf048)
0x0aa8 (0xf554)
Not Used
DIO
3
0x0078 (0xf03c)
0x0ba8 (0xf5d4)
Not Used
Not Used
7.1
Digital Descriptor
The SP-013 configures the sensors based on the factory device list and user-specified list index. The Sensor
Configuration and Sensor Device fields may be written to provide control of the overall function of the channel and
the signal types used.
7.1.1 Digital Descriptor
Offset
Name
Value
Description
0x00
Sensor Type
0x??
DIO, FREQUENCY, WIDTH, DUTY_CYCLE, DELAY, or
COUNT – set by Sensor Type field in Configuration
byte.
0x01
Data Type/Format
0x46
Float, Writeable
0x02
Configuration
0x??
Determines channel and Measurement Type
0x03
Sensor Device
0x??
Determines DIO signal types
0x04
UOMR
“??”
Units of measure