7.2.1.1 Process Measurement Types
The Process interface provides a measurement dependent on the input range/type selected. The units of
measure may be changed by the user.
Sensor Type SI Derived Units
Measurement
0x11
mV
Process Voltage (0 - 1.0 V, 0 – 2.0 V)
0x13
mA
Process Current (0-24 mA current loop, common return)
7.2.1.2 Process Input Data Type/Format
Process Input Data Type/Format
7
6
5
4
3
2
1
0
Smart
Sensor Writeable
Factory
Calibrate
Reserved
Data Type
0
0
?
0
0x06 = Float
7.2.1.2.1 Data Type
The 4-bit Data Type field determines the type of data of the specific sensor.
7.2.1.2.2 Factory Calibrate
Factory calibration is available for the process inputs. Clearing this bit will disable the factory
calibration values.
7.2.1.2.3 Writeable
The writeable bit is cleared, indicating that the sensor values may not be overwritten.
7.2.1.3 Process Input Configuration
Process Input Configuration
7
6
5
4
3
2
1
0
Available
Channel
Scaling
Lock
Sensor Range / Type
0
0*
?
?
(See Below)
7.2.1.3.1 Sensor Range / Type
Sensor
Range/Type
Sensor Input Type (Range)
Measurement Type
0x01
0-24 mA
0x13
Current (mA)
0x03
0-1.0 Vdc
0x11
Millivolts (mV)
0x09
0-2.0 Vdc
0x11
Millivolts (mV)
7.2.1.3.2 Lock
If set, the user-specified units of measure string (4 character maximum) will be used in place of
the default units of measure.
7.2.1.3.3 Apply Scaling
If set, the user-defined Offset and Gain values will be used to adjust the sensor reading:
Result = (Raw Reading * Gain) + Offset
7.2.1.3.4 Assigned
The Assigned bit will always read as 0.
7.2.1.3.5 Available
The Available bit will always read as 0.