11
Getting Started
(continued)
Step Two
LVCN414-SW SOFTWARE VS. DISPLAY CONFIGURATION
LVU700 series can be configured using either the free LVCN414-SW software and USB
®
Fob or with the
internal display module. Either method will accomplish the goal of sensor configuration. Changes to the
configuration can be made using the alternative method. Upon implementing one methodology, it is
recommended to complete the configuration before using the other methodology in making any adjustments.
LVU700 series can be configured before installation or after installation. The transmitter features non-volatile
memory, so any settings configured before installation will not be lost when the sensor is powered down. To
start, the following information is required:
Basic Tank Information
o
HEIGHT
(Sensor Height) – Distance from
the bottom of the tank to the bottom of the
sensor.
o
FILL-H
(Fill-Height) – Distance from the
bottom of the tank to the fill-height of the
liquid.
Power:
o
Provide input power to the LVU700 series
Note:
The
HEIGHT
and Fill-Height (
FILL-H
) settings also determine the 4 to 20 mA current span. The
HEIGHT
setting determines the 4mA position and the
FILL-H
setting determines the 20 mA position.