38
LVCN414-SW Software Appendix
(continued)
Section Seven
SENSOR CONFIGURATION (CONTINUED)
STARTUP CONDITION
This feature allows you to select the startup current when power is
first applied to the sensor. The sensor will consume the selected
power while it is acquiring the liquid level. When the correct level
has been identified, the output will adjust to the level output. Use
this feature to avoid false alarms with the controller when power is
first applied to the sensor.
Empty
- The current output will revert to the selected current
value for an empty condition.
o
4 mA at Bottom
- The sensor will output 4 mA while
the sensor powers up.
o
20 mA at Bottom
- The sensor will output 20 mA while
the sensor powers up.
Mid Tank (12 mA)
– The sensor will output 12 mA while the
sensor powers up.
Full
- The output will revert to the selected current value for a
full condition.
o
4 mA at Bottom
- The sensor will output 20 mA while
powering up.
o
20 mA at Bottom
- The sensor will output 4 mA while the
sensor powers up.
Overfill (22mA)
- The sensor will output 22mA while the
sensor powers up.
Note:
Right click on any tem to open the help menu.
Note:
To reset the configuration table, press the Clear Screen button