Configuration Using LVCN414-SW software
(continued)
Step Three
STEP 4 – DIMENSIONAL ENTRY:
Distance Mode (default):
Output of sensor is based on the distance (height of liquid) in the tank. Any
change in liquid level will reflect linearly to the current output. Note: Most applications will fall into this
category. For Volumetric outputs, refer to
VOLUMETRIC CONFIGURATION
on page 40. The two
values (Sensor Height and Fill-Height) below set the 4-20 mA current span for the sensor. Both values
will be set in the units shown under Height Units.
Sensor Height:
Sets the location for 4mA. It is based on the distance from the Empty level
position (bottom of tank) to the Measurement location for the sensor (bottom of sensor).
Fill-Height:
Sets the location for 20mA. It is based on the distance from the Empty level
position (bottom of tank) to the Full level position (see below).