16
Configuration Using LVCN414-SW software
Step Three
LVU700 series can be configured before installation. The transmitter features non-volatile memory, so any
setting configured before installation will not be lost when the switch is powered down. To configure, follow the
steps below:
1. Install LVCN414-SW software
a. Go to
omega.com/ftp
and select the installer program.
b. Review how USB
®
Fob interfaces with LVU700 series and your computer.
2. Measure the Tank
a. Begin by measuring the key tank and fitting dimensions.
b. Correct tank dimensions will result in accurate sensor measurement.
3. Sensor Configuration
a. Configures Loop Fail-Safe, Output at Empty & Startup Condition for the sensor.
4. Dimensional Entry
a. Distance Mode (default)
i. Basic information for operation (Sensor Height & Fill-Height).
5. Tank Level Confirmation
a. Confirm the values are accurate for the application.
6. Write to Unit
a. Uploads configuration into the sensor.
b. Access to a customer wiring diagram specific to the relay configuration.
Note:
When configuring LVU700 series, choose either the LVCN414-SW software or Push Button
method. Either method will accomplish the goal of sensor configuration. Changes to the
configuration can be made using the alternative method. When beginning with one method, it is
recommended to complete the configuration before using the other method to make any
adjustments.