87
• Alarm output (ALM1, ALM2 option)
• Output update cycle time: 500msec
• Relay contact output
×
2-pts SPST contact
Contact capacity:
AC220V/DC30V 1A
(Standard load)
(resistance load)
AC220V/DC30V 0.3A
(inductive load)
Minimum switching current: 100mA (DC24V)
Mechanical life:
12 million cycles (200
times/min.)
Electrical life:
100 thousand cycles
(Standard load, 20 times/
min.)
• Loop break alarm output (Option)
• Output update cycle time: 500msec
• Alarm setting range:
0.0 ~ 99 min 59 sec
• Relay contact output:
Alarm relay also used for
this
• Heater break alarm input signal (option)
1 ~ 30A:
CT (CTL-6-SF)
20 ~ 50A:
CT (CTL-12-S36-8F) used
*However, the output proportion cycle time must be 20
sec or above.
• Heater break alarm output (option)
• Output update cycle time:
500msec
• Alarm setting range:
1 ~ 50A
• The alarm output relay is also used for this output.
• Ramp/soak function (option)
Program pattern count:
1 pattern
Number of ramps/soaks
per pattern:
Maximum of 4
Time indication range:
0 hour 0 min - 799 hours
Memory backup:
EEP-ROM
OFF/run by digital input possible (only when start/reset
option is provided)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for FUZZY LOGIC CN4800
Page 2: ...M1791 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOUR...
Page 47: ...45 ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Page 100: ...98 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Page 101: ...99 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...