79
Output cycle time
Output proportion cycle time
The relay/SSR drive output delivers the manipulated variable (0 ~
100%) as the proportion of output-off time and output-on time. The
sum of output-on time and output-off time lengths, that is the on/off
cycle time is called the output proportion cycle time.
Output proportion cycle
OFF time
ON time
Setting procedure
(Output 1 side proportion cycle time)
The output proportion cycle time is
set in sec units (1 ~ 120 sec).
(Output 2 side proportion cycle time)
Normally the following output
proportion cycle time values must
be specified.
20 seconds
2 seconds
Relay output
SSR drive output
Parameter to be used
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com