background image

9

To set Retransmission to positive/negative slopes (a Retransmission board must be installed first): In 

Initial Setting Mode

  set

the 

  parameter, the last digit (Y) of xxxY indicates when Y=0 positive slope; when Y=1 negative slope.

To adjust the lower limit of Retransmission:

a

  Make sure the slope of Retransmission is positive.

b

  Set lower limit value larger than the display value: In

Initial Setting Mode

set the value in 

larger than the display value 

(PV). 

c

  Input the analog value to meter, check the meter and adjust the analog input value: In 

Regulation Mode

, enter the new value 

into 

. For example, if the range is 4~20mA, the new value will be 4mA. 

To adjust the upper limit Retransmission:

a

  Make sure the slope of Retransmission is positive.

b

  Set upper limit value smaller than the display value: In

Initial Setting Mode

set the value in

  smaller than the display 

value (PV). 

d

  Input the analog value to meter,check the meter and adjust the analog input value: In 

Regulation Mode

, enter the new value 

into 

. For example, if the range is 4~20mA, the new value will be 4mA. 

 Check the Firmware Version and Output Type 

When the temperature controller is ON, the PV and SV display will shows firmware version, output type and accessory functions in first 3 
seconds.   

PV (first 3 digits) indicates the firmware version. Ex: 110 indicates firmware version V1.10.

PV (4

th

 digit) indicates the function of accessory 1.

C: RS485 Communication      E: EVENT3 Input

SV (frist 2 digits) indicates the output type of OUT1 and OUT2.
N: No function      V: Voltage pulse output      R: Relay output      C: Current output
L: Linear voltage output      S: SSR output

SV (3

rd

 digit) indicates the function of accessory 2.

N: No function      C: CT measure      E: EVENT1 input      R: REMOTE input

SV (4

th 

digit) indicates the function of accessory 3.

N: No function      C: CT measure      E: EVENT2 input      R: RETRANSMISSION output

 Selection for Heating/Cooling/Alarm/Dual Loop Output Control 

CND

3 series offers 1 set of Output Control (OUT1) that is built-in internally and 2 sets of Alarm Output(ALARM1

 

and

 

ALARM2). User 

can also

 

purchase a 2

nd

 set of Output Control (OUT2) or a 3

rd

 set of Alarm Output (ALARM3). 

Using 1 set of Output Control :

In

Initial Setting Mode

, sets

  to Heating (H1) or Cooling(C1) mode. 

Using 2

nd

 set of Output Control:

When the 2

nd

 set of output control (OUT2) is used as a 3

rd

 set of arlarm (ALARM3), set 

  to H Alarm 3(H1A2) or

C Alarm 3(C1A2) in 

Initial Setting Mode

.

OUT2 output types in relay, voltage pulse, analog current, linear voltage and SSR output can all be used for ALARM ON-OFF. For
example, OUT2 is set to analog current output. It outputs 4mA when alarm is OFF and outputs 20mA when alarm is ON.

When  the  2

nd

  set  of  output  control  (OUT2)  is  used  as  dual  output  control,  set 

  to  heating  (H1H2);  cooling  (C1C2);

Heating/Cooling(H1C2) or Cooling/Heating (C1H2) control mode in

Initial Setting Mode

.

The Dead Band parameter 

  is automatically enabled when the temperature controller is in dual output control. As shown

in the diagram follow. The purpose of Dead Band function is to reduce the energy wastage of frequent heating/cooling actions. For
example, if SV = 100 degree and 

  = 2.0, there will be no output when the temperature is between 99~101°C..

Output of 

  when in ON-OFF control mode (Ctrl=ON-OFF control):

Adjust heating hysteresis

 

Adjust cooling hysteresis

 

Hea

ting 

Cooling 

Set Point 

Summary of Contents for CND3 Series

Page 1: ...CND3 Series Temperature Controller www omegamanual info Shop online at omega com For latest product manuals User sGuide e mail info omega com...

Page 2: ...rves the right to alter specifications without notice U S A Headquarters Servicing North America Omega Engineering Inc Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Page 3: ...or connecting the thermocouple wires 6 Please use wires with resistance when extending or connecting a platinum resistance thermometer RTD 7 Please keep the wire as short as possible when wiring a pl...

Page 4: ...Note Not all combinations may be available Check website under All Models to see list of available models...

Page 5: ...perature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller g...

Page 6: ...for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper li...

Page 7: ...will select P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY 2PID this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 Wh...

Page 8: ...eters into the selected PID group Select the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press Set up the 5 th PID temperature value press Set up the 0 th p...

Page 9: ...to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Settin...

Page 10: ...put 4 20mA or linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode...

Page 11: ...ent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of acc...

Page 12: ...e Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential numbe...

Page 13: ...Y position of parameter in Initial Setting Mode e g xxxY Y is 0 or 1 0 normal 1 power off saving Note When any settings or changes of the program parameters are made please save the settings changes t...

Page 14: ...adjustment by parameter in Regulation Mode Remote lower limit Setting Remote lower limit by parameter in Regulation Mode Remote higher limit Setting Remote higher limit by parameter in Regulation Mode...

Page 15: ...Initial Setting Mode To set for heating or cooling control Select desired output control by parameter in Initial Setting Mode If no board is inserted in Output2 selection items are H1 C1 H for heating...

Page 16: ...and the AT LED in the panel goes out The calculated PID parameters are displayed in and of which their content can be revised by the user Automatic switching over Multiple PID sets Set parameter to 0...

Page 17: ...g Set a value corresponding to Y position by parameter in Initial Setting Mode such as xxYx Y can be 0 or 1 0 30A 1 100A CT2 100A setting Set a value corresponding to Y position by parameter in Initia...

Page 18: ...on F1 F2 button can be used to switch between PID and MANUAL control mode ALRS Selecting this function F1 F2 button can be used to reset Alarm Hold status SV2 Selecting this function F1 F2 button can...

Page 19: ...will return to PV SV display mode 3 Enter the new password two times in the screen The screen will return to PV SV display mode with the keys unlocked If the two entries of password are not the same...

Page 20: ...if PV value is lower than the setting value SV AL H This alarm output is OFF when PV value is higher than the setting value SV AL L ON OFF SV AL H SV AL L SV 9 Disconnection Alarm This alarm output op...

Page 21: ...PV Measuring unit is 0 1 updated one time in 0 1 second The following reading value display indicates error occurs 8002H Initial process Temperature value is not got yet 8003H Temperature sensor is n...

Page 22: ...r 0 15 1032H Remaining time of the executed step second Only read 1033H Remaining time of the executed step minute Only read 1034H No of currently executed step Only read 1035H No of currently execute...

Page 23: ...Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 1119H Adjust Lower Limit of Analog Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 111AH Adjust Retransmission...

Page 24: ...Starting data address 10H 08H Starting data address 10H 08H 00H 10H 01H 10H 01H 10H Number of data word Bit 00H 00H Start address data 1000H 081xH 01H 17H Data content 03H FFH Data content 03H FFH 02H...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...http www omega com to contact OMEGA Engineering Inc 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 USA Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada on...

Reviews: