20

2nd output group 

1012H 

Output value read and write of 

Output 1 

Unit is 0.1%, write operation is valid under manual tuning mode only. 

1013H 

Output value read and write of 

Output 2 

Unit is 0.1%, write operation is valid under manual tuning mode only. 

1016H 

Temperature regulation value 

-99.9 ~ +99.9. Unit is 0.1

1017H 

Analog decimal setting 

0 ~ 3 

101CH 

PID parameter selection 

0~5/AUTO 

101DH 

SV value corresponded to PID 

value 

Only valid within available range, unit: 0.1 scale 

1020H 

Alarm 1 type 

Please refer to the contents of the “Alarm Outputs” for detail 

1021H 

Alarm 2 type 

Please refer to the contents of the “Alarm Outputs” for detail 

1022H 

Alarm 3 type 

Please refer to the contents of the “Alarm Outputs” for detail 

1024H 

Upper-limit alarm 1 

Please refer to the contents of the “Alarm Outputs” for detail 

1025H 

Lower-limit alarm 1 

Please refer to the contents of the “Alarm Outputs” for detail 

1026H 

Upper-limit alarm 2 

Please refer to the contents of the “Alarm Outputs” for detail 

1027H 

Lower-limit alarm 2 

Please refer to the contents of the “Alarm Outputs” for detail 

1028H 

Upper-limit alarm 3 

Please refer to the contents of the “Alarm Outputs” for detail 

1029H 

Lower-limit alarm 3 

Please refer to the contents of the “Alarm Outputs” for detail 

102AH 

Read LED Status 

b0: ALM3, b1: ALM2, b2: 

, b3:

 ℉

, b4: ALM1, b5: OUT2, b6:OUT1, b7: AT 

102BH 

Read Pushbutton Status 

b1: F2, b2: Up, b3: Loop,    b5: F1, b6: Down, b7: Set, 0: press down key 

102CH 

Setting lock status 

102FH 

Software version 

V1.00 indicates 0x100 

1030H 

Start pattern number 

0 ~ 15 

1032H 

Remaining time of the executed 

step (second) 

Only read 

1033H 

Remaining time of the executed 

step (minute) 

Only read 

1034H 

No. of currently executed step 

Only read 

1035H 

No. of currently executed pattern  Only read 

1036H 

Read dynamic value in 

programmable control 

Only read 

1039H 

Communication write 

0: Disable (default), 1: Enable 

103AH 

Temperature unit display 

selection 

0:  , 1:   / 

linear input (default) 

103BH 

AT setting 

0: OFF (default), 1: ON 

103CH 

Control RUN/STOP setting 

0: STOP, 1: RUN (default), 2:END (program mode), 3: HOLD (program mode) 

101FH 

Start step number 

0 ~ 15 

1200H~13FFH 

Pattern 0~15 temperature set 

point setting (Even number) 
Pattern 0~15 execution time 

setting (Odd number) 

-999 ~ 9999
Time: 0 ~ 900

1 minute per scale

1400H~140FH  Actual number of step setting 

inside the corresponding pattern 

0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N 

1410H~141FH 

Cycle  number  for  repeating  the 

execution  of  the  correspond 

pattern 

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times 

1420H~142FH  Link pattern number setting of 

the correspond pattern 

0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the 

program end and execution end. 0~15 indicates the next execution pattern 

number after executing the current pattern 

Address 

Content 

Definition 

1100H 

Adjust Temperature Gain 

1101H 

Temperature Filter Range 

Range of temperature filter: 10~1000, unit: 0.01 

, default: 100(1.0

)

 

1102H 

Temperature Filter Factor 

Setting range: 0~50, default: 8 

1103H 

Reverse Output 

Bit1: output 2, Bit0: output 1 

1104H 

Slope of Temperature Increase 

Unit: 0.1 /

min or 0.1

/sec (refer to CommunicationAddress 1124H) 

1105H 

Remote Input Type Selection 

0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V 

Summary of Contents for CND3 Series

Page 1: ...CND3 Series Temperature Controller www omegamanual info Shop online at omega com For latest product manuals User sGuide e mail info omega com...

Page 2: ...rves the right to alter specifications without notice U S A Headquarters Servicing North America Omega Engineering Inc Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Page 3: ...or connecting the thermocouple wires 6 Please use wires with resistance when extending or connecting a platinum resistance thermometer RTD 7 Please keep the wire as short as possible when wiring a pl...

Page 4: ...Note Not all combinations may be available Check website under All Models to see list of available models...

Page 5: ...perature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller g...

Page 6: ...for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper li...

Page 7: ...will select P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY 2PID this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 Wh...

Page 8: ...eters into the selected PID group Select the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press Set up the 5 th PID temperature value press Set up the 0 th p...

Page 9: ...to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Settin...

Page 10: ...put 4 20mA or linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode...

Page 11: ...ent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of acc...

Page 12: ...e Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential numbe...

Page 13: ...Y position of parameter in Initial Setting Mode e g xxxY Y is 0 or 1 0 normal 1 power off saving Note When any settings or changes of the program parameters are made please save the settings changes t...

Page 14: ...adjustment by parameter in Regulation Mode Remote lower limit Setting Remote lower limit by parameter in Regulation Mode Remote higher limit Setting Remote higher limit by parameter in Regulation Mode...

Page 15: ...Initial Setting Mode To set for heating or cooling control Select desired output control by parameter in Initial Setting Mode If no board is inserted in Output2 selection items are H1 C1 H for heating...

Page 16: ...and the AT LED in the panel goes out The calculated PID parameters are displayed in and of which their content can be revised by the user Automatic switching over Multiple PID sets Set parameter to 0...

Page 17: ...g Set a value corresponding to Y position by parameter in Initial Setting Mode such as xxYx Y can be 0 or 1 0 30A 1 100A CT2 100A setting Set a value corresponding to Y position by parameter in Initia...

Page 18: ...on F1 F2 button can be used to switch between PID and MANUAL control mode ALRS Selecting this function F1 F2 button can be used to reset Alarm Hold status SV2 Selecting this function F1 F2 button can...

Page 19: ...will return to PV SV display mode 3 Enter the new password two times in the screen The screen will return to PV SV display mode with the keys unlocked If the two entries of password are not the same...

Page 20: ...if PV value is lower than the setting value SV AL H This alarm output is OFF when PV value is higher than the setting value SV AL L ON OFF SV AL H SV AL L SV 9 Disconnection Alarm This alarm output op...

Page 21: ...PV Measuring unit is 0 1 updated one time in 0 1 second The following reading value display indicates error occurs 8002H Initial process Temperature value is not got yet 8003H Temperature sensor is n...

Page 22: ...r 0 15 1032H Remaining time of the executed step second Only read 1033H Remaining time of the executed step minute Only read 1034H No of currently executed step Only read 1035H No of currently execute...