  EVENT inputs/ CT function (optional) 1 

0: None, 1: Event Input3, 2: RS-485 Communication 

  EVENT inputs/ CT function (optional) 2 

0: None, 1: Event Input2, 2: CT measure input2.

  EVENT inputs/ CT function (optional) 3 

0: None, 1: Event Input1, 2: CT measure input1. 

 

Specifications 

Input Voltage 

80 ~ 260Vac 50/60Hz; 24Vac 50/60Hz ±10%; 24 Vdc ±10% 

Power Consumption 

8VA max. 

Display Method 

LCD display. Process value (PV): Yellow color, Set point (SV): Green color 

Sensor Type 

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK   
(Thermal couple measuring location are not intended to be directly connected to the MAINS supply.) 
3-wire Platinum RTD: Pt100, JPt100
Resistance: Cu50, Ni120 
Analog input: 0 ~ 5Vdc, 0 ~ 10Vdc, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mVdc 

Control Mode 

PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF 

Control Output 

Relay output: Max. load 250Vac, 5A resistive load 
Voltage pulse output: 12Vdc, Max. output current 40mA 
Current output: DC 4 ~ 20m A output (Load resistance: Max. 500Ω) 
Analog voltage output: 0 ~ 10Vdc 

Alarm Output Type 

Relay output: Max. load 250Vac, 3A resistive load 

Display Accuracy 

0 or 1 digit to the right of the decimal point (selectable) 

Sampling Rate 

Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan 

Vibration Resistance 

10 to 55Hz, 10m/s

2

 for 10min, each in X, Y and Z directions 

Shock Resistance 

Max. 300m/ s

2

, 3 times in each 3 axes, 6 directions 

Ambient Temperature 

0°C ~ +50°C 

Storage Temperature 

-20°C ~ +65°C

Altitude 

Max. 2000m 

Relative Humidity 

35% ~ 80% RH

non-condensing

 

 Operation 

There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation
mode. Press the 

  key to switch to regulation mode. If the 

  key is pressed for more than 3 seconds, controller will switch to the 

initial setting mode. Pressing the 

  key while in the regulation mode or initial setting mode, forces the controller to return to the 

operation mode.. 

PV/SV: Sets the temperature set point and displays the temperature process value. Use

  keys to set the temperature set 

point.

Setting method: While in any function mode, press the

  key to select the desired function and use 

  keys to change 

settings. Press 

  key to save the changes.

The flow chart below shows how to switch the settings and internal functions:

Regulation Mode

Operation Mode

Initial Setting Mode

Press       key less than 3 sec

Press       key

Press       key more than 3 sec

Press       key

Operation 

Mode

Parameter Setting: 

Display 

Description 

Factory Setting

Use 

  to set temperature set point, use 

  to switch between the display parameter 

RUN/STOP: Control setting RUN or STOP 

RUN 

PATTERN: Start pattern setting (set control mode to PROG mode) 

STEP: Start step setting (set control mode to PROG mode) 

SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point) 

LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed) 

OFF 

ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode) 

4.0 

ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode) 

4.0 

Summary of Contents for CND3 Series

Page 1: ...CND3 Series Temperature Controller www omegamanual info Shop online at omega com For latest product manuals User sGuide e mail info omega com...

Page 2: ...rves the right to alter specifications without notice U S A Headquarters Servicing North America Omega Engineering Inc Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Page 3: ...or connecting the thermocouple wires 6 Please use wires with resistance when extending or connecting a platinum resistance thermometer RTD 7 Please keep the wire as short as possible when wiring a pl...

Page 4: ...Note Not all combinations may be available Check website under All Models to see list of available models...

Page 5: ...perature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller g...

Page 6: ...for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper li...

Page 7: ...will select P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY 2PID this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 Wh...

Page 8: ...eters into the selected PID group Select the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press Set up the 5 th PID temperature value press Set up the 0 th p...

Page 9: ...to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Settin...

Page 10: ...put 4 20mA or linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode...

Page 11: ...ent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of acc...

Page 12: ...e Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential numbe...

Page 13: ...Y position of parameter in Initial Setting Mode e g xxxY Y is 0 or 1 0 normal 1 power off saving Note When any settings or changes of the program parameters are made please save the settings changes t...

Page 14: ...adjustment by parameter in Regulation Mode Remote lower limit Setting Remote lower limit by parameter in Regulation Mode Remote higher limit Setting Remote higher limit by parameter in Regulation Mode...

Page 15: ...Initial Setting Mode To set for heating or cooling control Select desired output control by parameter in Initial Setting Mode If no board is inserted in Output2 selection items are H1 C1 H for heating...

Page 16: ...and the AT LED in the panel goes out The calculated PID parameters are displayed in and of which their content can be revised by the user Automatic switching over Multiple PID sets Set parameter to 0...

Page 17: ...g Set a value corresponding to Y position by parameter in Initial Setting Mode such as xxYx Y can be 0 or 1 0 30A 1 100A CT2 100A setting Set a value corresponding to Y position by parameter in Initia...

Page 18: ...on F1 F2 button can be used to switch between PID and MANUAL control mode ALRS Selecting this function F1 F2 button can be used to reset Alarm Hold status SV2 Selecting this function F1 F2 button can...

Page 19: ...will return to PV SV display mode 3 Enter the new password two times in the screen The screen will return to PV SV display mode with the keys unlocked If the two entries of password are not the same...

Page 20: ...if PV value is lower than the setting value SV AL H This alarm output is OFF when PV value is higher than the setting value SV AL L ON OFF SV AL H SV AL L SV 9 Disconnection Alarm This alarm output op...

Page 21: ...PV Measuring unit is 0 1 updated one time in 0 1 second The following reading value display indicates error occurs 8002H Initial process Temperature value is not got yet 8003H Temperature sensor is n...

Page 22: ...r 0 15 1032H Remaining time of the executed step second Only read 1033H Remaining time of the executed step minute Only read 1034H No of currently executed step Only read 1035H No of currently execute...

Page 23: ...Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 1119H Adjust Lower Limit of Analog Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 111AH Adjust Retransmission...

Page 24: ...Starting data address 10H 08H Starting data address 10H 08H 00H 10H 01H 10H 01H 10H Number of data word Bit 00H 00H Start address data 1000H 081xH 01H 17H Data content 03H FFH Data content 03H FFH 02H...