5.11 Input/ Output
This menu displays state of input and outputs.
The input displays condition of external switch that pulls the input down. If the switch is
closed then the input is displayed set and the dryer operates. If the switch is opened then
the input is displayed cleared and the dryer is in standby.
The output displays condition of the output relay.
The bottom row displays which valve is energized at the moment.
Information provided by this menu is valuable during troubleshooting
5.12 Set standby
The dryer enters standby when the input is opened. If stand by is not needed, the input
terminal must be bridged. Otherwise, the input is connected to voltage free contact in some
external device or SCADA.
Figure: Connection of input to an external device
Figure: Input terminals are bridged to disable standby
The yellow indicator LED is connected to this input and it is lit up when the terminals are
open.