27
Figure: Example of connection of output to typical SCADA
In this menu, the draining can be triggered manually by pressing cancel key.
In the Timer Drain Menu, it is displayed when the condensate is going to be released. If On
Period of timer is set to zero, the timer drain function is disabled.
5.10 Timer Drain Setting
Operation of the timer drain is set by on and off periods in the Timer Drain Setting menu.
The off period can be selected in range from 30 seconds to 45 minutes. The on period can be
set from 1 second to 7 seconds. Besides, It can be set to zero to disable timer drain.
12
11
drain
Controller
Dryer
inlet
**** Timer Drain ****
Set
>Period OFF: 00:30
Period ON: --:--
2 sec.
**** Timer Drain ****
Set
Period OFF: > 00:30
Period ON: --:--
**** Timer Drain ****
Set
Period OFF: 00:30
>Period ON: --:--
**** Timer Drain ****
Set
Period OFF: 00:30
Period ON: > 00:01