26
Figure: Example of connection of output to typical SCADA
In case of internal error, the output is cleared in both modes. Obviously, the output is
cleared when dryer is switched off.
5.9 Timer drain
There must be a filter at the inlet of the dryer. This filter removes condensed water, droplets
of oil etc. from the air that enters the dryer. This is necessary to keep desiccant fit for the
job. The water that collects in the filter housing must be discharged. The job can be done by
manual drain, which is quite an obligation for operator. Instead, an automatic or electronic
drain can be used. Besides, the dryer can control one electromagnetic valve to discharge
condensate by itself. It operates as timer drain. Additionally, the dryer does not operate this
valve in standby mode. Contrary to stand alone timer drain, no compressed air is lost during
standby this way.
14
15
13
input
Controller
Dryer
24Vdc
PLC
SCADA
***** Dew Point *****
Set
>Alarm: -30°C
Output: Dryer Active
2 sec.
***** Dew Point *****
Set
Alarm: > -30°C
Output: Dryer Active
***** Dew Point *****
Set
Alarm: -30°C
>Output: Dryer Active
***** Dew Point *****
Set
Alarm: -30°C
Output:>Dryer Active
***** Dew Point *****
Set
Alarm: -30°C
Output:>Dew Point OK
Summary of Contents for A-DRY Series
Page 2: ...2...
Page 16: ...16...
Page 37: ...37 5 9 1...
Page 46: ...46 13 6 13 7...
Page 48: ...48 Normally open valve Normally closed valve 13 10 13 11...
Page 50: ...50 13 15...
Page 56: ...56 14 6 14 7...
Page 63: ...63 16 Maintenance record TYPE OF MAINTENANCE DATE SIGNATURE NOTES Commissioned...
Page 64: ...64...