iTrans Fixed Point Single/Dual Gas Monitor
ModBus Interface
(P/N: 77023554-1)
iTrans User Manual
6-1
M
OD
B
US
I
NTERFACE
Chapter
6
6.1. Introduction
When programming the ModBus ID address on the
electronics module
or on the smart sensor board, use the binary reference chart on the following page.
A “1” represents “ON” on the switch bank, and position 1 of the switch bank
represents the right most binary digit (LSB).
ModBus characteristics for the
are listed below.
Table 6-1. ModBus Characteristics for the
Gas Monitor
Characteristic
Description
Hardware
2-wire mode (not 4-wire)
Baud Rate
9600
Electrical Standard
TIA/EIA-485
Transmission Mode
RTU mode (not ASCII)
Message Coding System
8-bit
Start Bits
1
Data Bits
8 (LSB sent first)
Parity Bits
0
Stop Bits
1
Important:
When commissioning master and slave units on a ModBus network, it
is critical to ensure that every device on the ModBus network must have a unique
address. Otherwise, abnormal behavior of the entire serial bus can occur.
6.2. Sample Gas Reading via ModBus Network
To get a gas reading for Channel 1, you must read register 40102. This register
holds the gas reading in ppm.
Summary of Contents for iTrans
Page 13: ...iTrans Fixed Point Single Dual Gas Monitor Introduction P N 77023554 1 iTrans User Manual 1 7...
Page 14: ......
Page 36: ......
Page 54: ...Operation iTrans Fixed Point Single Dual Gas Monitor 5 18 iTrans User Manual P N 77023554 1...
Page 78: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 iTrans User Manual P N 77023554 1...
Page 80: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 iTrans User Manual P N 77023554 1...
Page 86: ......
Page 87: ......