iTrans Fixed Point Single/Dual Gas Monitor
System Wiring
(P/N: 77023554-1)
iTrans User Manual
4-3
Figure 4-1. Alarm Relay Connectors J6, J5 and J1
4.4. Power and Output Wiring (J1)
Connect the
power and signal wires to the appropriate wiring terminals
as follows.
24 V:
Connect 24 VDC (12-28 VDC) supply power
CH 1:
Channel 1, 4-20 mA output signal
CH 2:
Channel 2, 4-20 mA output signal
GND:
DC return
Figure 4-2. Power and Signal Connector J1 on the
NOTE:
Use supplied green conductor for enclosure ground. Public 485 GND is
to be used for ModBus digital ground.
NOTE:
The
is a 3- or 4-wire 4-20 mA device. For dual sensor
configuration you must have a second 4-20 mA signal wire pulled to the unit.
Summary of Contents for iTrans
Page 13: ...iTrans Fixed Point Single Dual Gas Monitor Introduction P N 77023554 1 iTrans User Manual 1 7...
Page 14: ......
Page 36: ......
Page 54: ...Operation iTrans Fixed Point Single Dual Gas Monitor 5 18 iTrans User Manual P N 77023554 1...
Page 78: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 iTrans User Manual P N 77023554 1...
Page 80: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 iTrans User Manual P N 77023554 1...
Page 86: ......
Page 87: ......