iTrans Fixed Point Single/Dual Gas Monitor
Installation
(P/N: 77023554-1)
iTrans User Manual
3-1
I
NSTALLATION
Chapter
3
3.1. Introduction
The
can be mounted in one of two ways. The unit can be wall-mounted
using the wall mounting holes in the enclosure, or it can be mounted onto a column
using U-bolts. Each of these options is discussed in this chapter. Be sure to
review the installation considerations before mounting the gas monitor.
3.2. Installation Considerations
Regardless of the installation type (wall mounting or column mounting), the
should be installed at or near the location of a possible leak or the source
of emissions. Installation height depends on the density of the gas being monitored.
Moreover, speed and direction of air flow, and relative position to potential leaking
points should also be considered.
IMPORTANT:
The
gas monitor must not be installed on vibrating or
heat generating sources.
3.3. Wall Mounting
If your application is best addressed using a wall-mounted gas monitor, then use
the four 8 mm mounting holes in the enclosure to secure the to an appropriate
location on the wall. Refer to Figure 3-1.
3.4. Column Mounting
If your application is best addressed using a column-mounted gas monitor, then use
the four 8 mm mounting holes and two U-bolts to secure the to an appropriately
located segment of a target pipe or conduit. Refer to Figure 3-2.
Summary of Contents for iTrans
Page 13: ...iTrans Fixed Point Single Dual Gas Monitor Introduction P N 77023554 1 iTrans User Manual 1 7...
Page 14: ......
Page 36: ......
Page 54: ...Operation iTrans Fixed Point Single Dual Gas Monitor 5 18 iTrans User Manual P N 77023554 1...
Page 78: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 iTrans User Manual P N 77023554 1...
Page 80: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 iTrans User Manual P N 77023554 1...
Page 86: ......
Page 87: ......