29
8 System settings
System settings include date and time, language, SMS and net-
work settings, display settings and device type information.
Main menu
DHW Control circuit
Alarms
System settings
Service
>
>
>
>
System settings
Time 17:01
Date 24.04.2021
Daylight saving time In use
Language English
SMS settings
Network settings
Display settings
Type info
Lock code Not in use
>
>
>
>
>
>
>
>
>
Date
Thu 24.04.2021
dd.mm.yyyy
Enter day:
Time
19:44
hh:mm
Enter hours
8.1 Setting date, time and language
It is important that date and time are correct. The date and time are
used e. g. in time programs as well as alarm indication and routing.
The S203 clock takes daylight savings and leap years into account
automatically. The clock has a backup for power outages lasting at
least three days.
1. Set hours and press OK to accept.
2. Set minutes and press OK to accept.
3. To exit without saving and changes press Esc.
1. Set day and press OK to accept (name of weekday is updated au-
tomatically).
2. Set month and press OK to accept.
3. Set year and press OK to accept.
4. To exit without saving and changes press Esc.
The language of the user interface can be change here.
System settings > Time
System settings > Date
System settings > Language
Language
English
Suomi
Svenska
The controller will automatically be switched to to daylight saving time
and to standard time, if the selection “In use” is made.
System settings
>
Daylight saving time
Daylight saving time
In use
Not in use
Alarm sound
Alarm sound
Off
On
You can take the alarm sound off, if you want.
On:
Information about the activated alarm is shown on the display. Also a continous
alarm signal is given. If the controller has a number of unacknowledged alarms and
you acknowledge the last one, the one before it will appear on the display. When
all active alarms have been acknowledged, the alarm window closes and the alarm
sound goes off.
Off:
The controller displays information on activating the alarm, but the controller
does not include an alarm signal.