24
Geothermal heating
Accumulator upper part MIN = 55.0°C/
Accumulator lower part MIN= 45.0°C
GEOTHERMAL HEATING
Send a message: Geothermal heating.
The controller sends main settings to your mobile phone. Editing the setting
values: write the new setting in place of the old setting and send a message
back to the controller. The controller sends back the setting as a confirmation.
Setting values
Setting
Factory
setting
Setting
area
Explanation
Geopro SH
GH control
Compres-
sor and
El.heater
You can choose whether the ground heating is controlled by a
compressor only or by an electric heater only, or whether an elec-
tric heater is used with the compressor.
Boiler Top winter
65
30... 75 °C Top of the accumulator setting value when the outside temperatu-
re is < -20°C.
Boiler Top summer
55
30... 75 °C Top of the accumulator setting value when the outside temperatu-
re is > +20°C.
Boiler Down MIN limit
30
30... 55 °C Minimum temperature of the lower part of the accumulator (Mi-
nimum temperature of the heating water leaving the geothermal
appliance)
Extra heating
Extra heating time
50
2
40...55°C
0... 6h
When the “Extra heating” button is pressed, the setting changes
from ”Boiler down MIN limit” to the “Extra heating” setting value for
the duration of the “Extra heating time” setting value.The tempera-
ture of lower part of the DHW boiler increase, which increases the
hot water capacity.
Wl.Heat start up delay
30
0 ... 120 min. The temperature of middle part of the accumulator can only
switch on the electric heater after the compressor has been run-
ning for the time set here (min).
Temperature Boiler Top
Calculated The temperature of the boiler top, which depends on the settings
for the ”BoilerTopWint and ”BoilerTopSumm” (see figure).
50
...
-30
-20
-10 0 10
20
30 Outd. t
°C
Upper part of the boiler
60
65
70
55
Boiler’s
Upper part setting
°C
The running times of the compressor and the electric
heater are shown here. The controls and modes that
affect the setting are presented on the service side.
Stauts
Tila
Restart delay
Heating resistor start delay
Hot gas blockig Off
Acc. lower part prevent start Off
Compressor running time xx h
Heating resistor ON time xx h
>
>
>
>
>
>
Status
6.2 Status
Geothermal heating-> Status