Description
Params. & Display
O2 Module
Displayed Values
Actual O2 Value
Actual O2 Value
O2 Setpoint
O2 Setting
SupplyAirTemp
Supply air
temperature in °C /
°F
FlueGasTemp
Flue gas
temperature °C / °F
CombEfficiency
Combustion
efficiency
QGO SensorTemp QCO-sensor
temperature °C / °F
QGO HeatingLoad Control value of
QGO... heating,
0,1%
QGO Resistance
Internal resistance
of QGO's Nernst
cell
Self test is made at 23-intervals. Test requires constant O
2
level, for e.g. after pre-
purge or on steady load. If constant O
2
level is not reached within 24 hours, burner
control locks down operation load to reach constant O
2
level for next test. If burner is in
stand by mode, test is made during next burner start-up.
Flue gases containing aggressive acids may strongly shorten oxygen
sensor durability.
O
2
module can be connected with burner combustion air and flue gas temperature
sensors. If sensors are connected, warning is displayed when flue gas temperature is
too high, and combustion efficiency will be calculated and displayed.
Check that oxygen value and sensor temperature, heating efficiency
and resistance values are displayed. If temperature sensors are
connected and activated, values should be displayed.
4.20 Manual start-up and program stop in pre-purge position
Program stop
With burner control
ProgramStop
parameter burner start-up can be stopped in
selected program phase, and servomotor position can be adjusted.
62 (129)
M5178 1647EN
Summary of Contents for GKP-350 M
Page 2: ......
Page 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Page 6: ...4 129 M5178 1647EN...
Page 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Page 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Page 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Page 132: ...130 129 M5178 1647EN...
Page 133: ......