QRI connection
QRI connection ver. 1
A
Black
X10-02 / 6
Signal line
B
Blue
X10-02 / 4
Reference line
C Brown
X10-02 / 2
Power line
2.4 Burner control technical data
Burner control
LMV5...
Mains voltage
120 VAC –15/+10 %
Locking during undervoltage conditions
< 96 VAC
Transformer / primary side
120 VAC
Transformer / side 1
12 VAC
Transformer / side 2
2 x 12 VAC
Mains frequency
50–60 Hz 6 %
Power consumption
< 30 W
Permissible input current / differential air pressure
switch
0.5 A / 230 VAC -15/+10 %
Permissible input current / status input
1.5 mA/120 VAC -15/+10 %
Perm. current rating of control terminals
● fan motor contactor
● burner failure
● ignition transformer
● gas valves
● oil valves
5 A / 120 VAC -15/+10 %
● 1 A/120 VAC -15/+10 %
● 1 A/120 VAC -15/+10 %
● 1.6 A/120 VAC -15/+10 %
● 1.6 A/120 VAC -15/+10 %
● 1.6 A/120 VAC -15/+10 %
Permissible operation ambient temperature
-20...+60 °C
-4...+140 °F
M5178 1647EN
15 (129)