Oil pump operating pressure (atomizing pressure) in light fuel oil is 2000 - 2500 kPa
(20 - 25bar).
Spill return nozzle Bergonzo CBM B5 AA
Table is applicable when atomizing viscosity is 12 mm²/s (cSt)
Nozzle No.
Max. throughput kg/h at oil pump pressure of
25 bar (2,5 MPa) when return line is closed
Min. throughput kg/h at oil
pump pressure of 25 bar (2,5
MPa) when return line pressure
is 3 bar (0,3 MPa)
450
450
90
500
500
100
600
600
120
700
700
140
800
800
160
900
900
180
For example: Nozzle CBM B5 AA No. 450, oil pump pressure 30 bar (3,0 MPa) ⇒
throughput of nozzle is:
450 kg/h x
30 bar
25 bar
~
~ 493 kg/h
PAINEKAAVA5 ver. 2
When viscosity increases the quantity of oil spraying from nozzle
increases approx. 5-15%.