4.22 Setting ratio curve
Curve points
There can be 15 curve points at the maximum.
Set curve points in the following menu level:
Params. & Display
RatioControl
GasSettings
CurveSettings
Point
Manual
Creating curve point individually
Current servomotor positions in degrees, frequency converter control and capacity in
percentages are shown at the right corner on display. Pointer is positioned at
Point
.
Curve point 1 ver. 3
Press
Enter
to scroll through stored curve points.
Curve point 2 ver. 3
The pointer is positioned at the colon below the
Point
text. After the colon, there is the
running number of the stored curve point.
Curve points are stored according to capacity from smallest to biggest. Curve points
can be added at any order. Scroll through curve points using the
Select -/+
buttons.
The unused curve point setting is
XXXX
and its running number is one number greater
than last stored curve point running number.
66 (129)
M5178 1647EN