Flow rates B0/–3 /brine in: 0, brine out: –3)
Condenser
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−3, W20/25
20
25
1.05
1.77
3.23
4.37
4.18
997.7
B0/−3, W30/35
30
35
1.02
1.71
3.11
4.23
4.18
994.9
B0/−3, W40/45
40
45
0.99
1.64
2.99
4.07
4.18
991.3
B0/−3, W47/55
47
55
0.61
0.99
1.79
2.44
4.18
987.6
B0/−3, W55/65
55
65
0.77
1.36
4.18
983.2
Condenser
flow rate, kg/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−3, W20/25
20
25
1045
1768
3226
4364
4.18
997.7
B0/−3, W30/35
30
35
1010
1697
3099
4206
4.18
994.9
B0/−3, W40/45
40
45
984
1629
2962
4030
4.18
991.3
B0/−3, W47/55
47
55
607
979
1764
2407
4.18
987.6
B0/−3, W55/65
55
65
753
1333
4.18
983.2
Evaporator
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−3, W20/25
20
25
1.50
2.56
4.58
6.05
4.21
968.1
B0/−3, W30/35
30
35
1.37
2.32
4.16
5.50
4.21
968.1
B0/−3, W40/45
40
45
1.22
2.07
3.70
4.91
4.21
968.1
B0/−3, W47/55
47
55
1.07
1.80
3.22
4.29
4.21
968.1
B0/−3, W55/65
55
65
1.50
2.67
4.21
968.1
Evaporator
flow rate, kg/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−3, W20/25
20
25
1454
2479
4433
5859
4.21
968.1
B0/−3, W30/35
30
35
1324
2249
4026
5329
4.21
968.1
B0/−3, W40/45
40
45
1183
2000
3580
4749
4.21
968.1
B0/−3, W47/55
47
55
1040
1743
3116
4153
4.21
968.1
B0/−3, W55/65
55
65
1451
2585
4.21
968.1