6.5 Operating conditions
The unit’s operating condition range is provided in the table and the diagram below.
The unit has been designed for use within the specified conditions. The unit’s
performance cannot be guaranteed outside these recommended conditions.
The heat pump’s automation system keeps the compressor’s rotation speed within
the compressor’s operating envelope. The available operating range depends on the
compressor’s rotation speed as well as the evaporator and condenser temperature. If
the unit’s output temperature e60 °C, the system will limit the compressor’s
speed in steps. At the highest output temperature (+68 °C), compressor speed and
heating capacity are kept at approximately 75% of the unit’s maximum speed and
power.
Minimum value
Maximum value
ECO I 7–25
absolute
recommended
absolute
recommended
Brine into the evaporator
°C
–6
–5
25
5
Brine out of the evaporator
°C
–10
-9
–
–
Temperature difference
across the evaporator
circuit
°C
1
–
5
4
Water into the condenser
°C
15
20
63
61
Water from the condenser
°C
18
25
68
67
Temperature difference
across the condenser
circuit
°C
3
5
20
15
DESIGN FLOW RATE
Evaporator Condenser
In
°C
0
+30
Out
°C
–3
+35
Heating capacity at full power
kW
18.7
24.4
Specific heat capacity
kJ/
(kg K)
4.21
4.18
Density
kg/m
3
968.1
994.9
Flow rate
m3/h
5.50
4.23
Flow rate
kg/h
5329
4206
Evaporator circuit fluid: mixture of water and ethanol, 28 mass-% ethanol (34 vol-%)
48 (54)
M8003 2219EN