Flow rates B0/–4 /brine in: 0, brine out: –4)
Condenser
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−4, W20/25
20
25
1.02
1.72
3.13
4.24
4.18
997.7
B0/−4, W30/35
30
35
0.99
1.66
3.02
4.10
4.18
994.9
B0/−4, W40/45
40
45
0.96
1.60
2.90
3.95
4.18
991.3
B0/−4, W47/55
47
55
0.60
0.97
1.74
2.37
4.18
987.6
B0/−4, W55/65
55
65
0.75
1.32
4.18
983.2
Condenser
flow rate, kg/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−4, W20/25
20
25
1014
1714
3125
4226
4.18
997.7
B0/−4, W30/35
30
35
981
1647
3006
4079
4.18
994.9
B0/−4, W40/45
40
45
957
1583
2877
3914
4.18
991.3
B0/−4, W47/55
47
55
591
953
1716
2341
4.18
987.6
B0/−4, W55/65
55
65
735
1299
4.18
983.2
Evaporator
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−4, W20/25
20
25
1.08
1.85
3.31
4.37
4.21
968.3
B0/−4, W30/35
30
35
0.99
1.68
3.00
3.97
4.21
968.3
B0/−4, W40/45
40
45
0.88
1.49
2.67
3.54
4.21
968.3
B0/−4, W47/55
47
55
0.78
1.30
2.32
3.09
4.21
968.3
B0/−4, W55/65
55
65
1.08
1.92
4.21
968.3
Evaporator
flow rate, kg/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B0/−4, W20/25
20
25
1050
1792
3202
4229
4.21
968.3
B0/−4, W30/35
30
35
955
1625
2907
3846
4.21
968.3
B0/−4, W40/45
40
45
854
1445
2584
3426
4.21
968.3
B0/−4, W47/55
47
55
751
1258
2248
2994
4.21
968.3
B0/−4, W55/65
55
65
1046
1863
4.21
968.3
M8003 2219EN