Flow rates B5/+2 (brine in: +5, brine out: +2)
Condenser
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B5/2, W20/25
20
25
1.22
2.07
3.78
5.12
4.18
997.7
B5/2, W30/35
30
35
1.17
1.98
3.62
4.92
4.18
994.9
B5/2, W40/45
40
45
1.14
1.89
3.45
4.70
4.18
991.3
B5/2, W47/55
47
55
0.70
1.13
2.05
2.80
4.18
987.6
B5/2, W55/65
55
65
0.87
1.54
4.18
983.2
Condenser
flow rate, kg/h
Water
in, °C
Water
out, °C
Min.
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B5/2, W20/25
20
25
1216
2061
3773
5108
4.18
997.7
B5/2, W30/35
30
35
1169
1968
3605
4894
4.18
994.9
B5/2, W40/45
40
45
1129
1875
3424
4661
4.18
991.3
B5/2, W47/55
47
55
689
1119
2025
2767
4.18
987.6
B5/2, W55/65
55
65
852
1518
4.18
983.2
Evaporator
flow rate, m
3
/h
Water
in, °C
Water
out, °C
Min.
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B5/2, W20/25
20
25
1.80
3.07
5.50
7.29
4.22
966.4
B5/2, W30/35
30
35
1.64
2.79
5.00
6.63
4.22
966.4
B5/2, W40/45
40
45
1.47
2.48
4.46
5.93
4.22
966.4
B5/2, W47/55
47
55
1.29
2.17
3.89
5.20
4.22
966.4
B5/2, W55/65
55
65
1.81
3.25
4.22
966.4
Evaporator
flow rate, kg/h
Water
in, °C
Water
out, °C
Min.
50 Hz
90 Hz
Max.
c
p
, kJ/
(kg K)
ρ, kg/
m
3
B5/2, W20/25
20
25
1743
2964
5316
7041
4.22
966.4
B5/2, W30/35
30
35
1588
2693
4834
6411
4.22
966.4
B5/2, W40/45
40
45
1420
2398
4307
5727
4.22
966.4
B5/2, W47/55
47
55
1248
2093
3761
5030
4.22
966.4
B5/2, W55/65
55
65
1749
3142
4.22
966.4
SCOP and SPF value
Climate
Average
(A)
Warm
(W)
Cold
(C)
References
City
Strasbourg,
France
Athens,
Greece
Helsinki,
Finland
Seasonal coefficient of performance
Space heating
SCOP
3
Low temperature application (max. flow
water temperature: 35 °C).
5.49
5.34
5.50
Average temperature application (max.
flow water temperature: 55 °C).
4.02
4.01
4.21
Heat pump Seasonal Performance Factor
(SPF value), Space heating
SPF
spaces
3, 4
Floor heating, max. flow temperature 35
°C
5.49
5.34
5.50
Radiator heating, max. flow temperature
55 °C
4.02
4.01
4.21
M8003 2219EN